Bulletin 100-50-6.1 –
Page 3
7 WORKING SETPOINTS and CONFIGURATION PARAMETERS
7.1 Working setpoints
7.2 Configuration parameters
Minimum
Maximum
U.M.
PSK201
Working Setpoints
r1
r2
°C/°F
0.0
working setpoints
Parameters
Minimum
Maximum
U.M.
PSK201
Working Setpoints
SP
r1
r2
°C/°F
0.0
working setpoints
Parameters
Minimum
Maximum
U.M.
PSK201
Temperature Inputs
CA1
-25.0
25.0
°C/°F
0.0
cabinet probe offset
P0
0
1
—
1
kind of probe
0 = PTC
1 = NTC
P1
0
1
—
1
display decimal point value during normal operation (Celsius mode only)
1 = YES
P2
0
1
—
0
unit of measure, temperature
0 = °C
1 = °F
Parameters
Minimum
Maximum
U.M.
PSK201
Setpoints
r0
0.1
15.0
°C/°F
2.0
working setpoint differential
r1
-99.0
r2
°C/°F
-50.0
minimum working setpoint
r2
r1
99.0
°C/°F
50.0
maximum working setpoint
Parameters
Minimum
Maximum
U.M.
PSK201
Compressor Protections
C0
0
240
min
0
compressor delay after turning on the controller
C2
0
240
min
3
minimum time the compressor remains turned off
Parameters
Minimum
Maximum
U.M.
PSK201
defrost
d0
0
99
h
8
defrost interval
0 = the defrost at intervals will never be activated
d3
0
99
min
30
defrost duration
0 = the defrost will never be activated
d4
0
1
—
0
defrost when you turn on the controller
1 = YES
d5
0
99
min
0
defrost delay when you turn on the controller (only if d4 = 1)
d6
0
1
—
1
temperature shown during the defrost
0 = cabinet temperature
1 = if, upon the activation of defrost, the cabinet temperature is below
“working se r0”, at most “working se r0”; if, upon the
activation of defrost, the cabinet temperature is above “working setpoint
+ r0”, at most the cabinet temperature to the defrost activation