Bulletin 100-50-6.2 –
Page 5
8.1 Configuration parameters (continued)
Parameters
Minimum
Maximum U.M.
dEF.
Temperature Inputs (continued)
A0
0
2
—
0
measured input used for the low temperature alarm
0 = cabinet temperature
1 = evaporator temperature
A1
-99.0
99.0
°C/°F
-10.0
temperature below which the low temperature alarm is activated; also look at A0 and A2
A2
0
2
—
1
kind of lower temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or “working setpoint - A1”; consider A1 without sign)
2 = absolute (or A1)
A4
-99.0
99.0
°C/°F
10.0
temperature above which the high temperature alarm is activated; also look at A3 and A5
A5
0
2
—
1
kind of upper temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or “working se A4”; consider A4 without sign)
2 = absolute (or A4)
A6
0
240
min
120
high temperature alarm delay since you turn on the controller (only if A3 = 0)
A7
0
240
min
15
temperature alarm delay
A8
0
240
min
15
high temperature alarm delay since the end of the after dripping evaporator fan delay
(only if A3 = 0)
A9
0
240
min
15
high temperature alarm delay since the deactivation of the door switch input (only
PSK223 and PSK233)
Parameters
Minimum
Maximum U.M.
dEF.
Evaporator Fan
F0
0
4
—
1
evaporator fan activity during the normal operation
0 = turned off
1 = turned on
2 = according to the compressor
3 = according to F1
4 = turned off if the compressor is turned off; according to F1 if the compressor is
turned on
F1
-99.0
99.0
°C/°F
-1.0
evaporator temperature above which the evaporator fan is turned off
(only if F0 = 3 or 4)
F2
0
2
—
0
evaporator fan activity during defrost and drip delay
0 = turned off
1 = turned on
2 = according to F0
F3
0
15
min
2
fan delay after evaporator drip completes
Parameters
Minimum
Maximum U.M.
dEF.
digital Inputs – Only PSK223 and PSK233
i0
0
3
—
2
kind of digital input
0 =
MULTIPURPOSE INPUT
- in this case look at parameters i1, i5, i7, i8 and i9
1 =
RESERVEd
2 =
dOOR SWITCH INPUT
- in this case look at parameters i1, i2 and i3; the
activation of the input will turn off the evaporator fan (for at most time i3 or until
the input is deactivated)
3 =
dOOR SWITCH INPUT
- in this case look at parameters i1, i2 and i3; the
activation of the input will turn off the compressor and the evaporator fan (for at
most time i3 or until the input is deactivated)
i1
0
2
—
0
digital input contact type
0 = NO (the input will be active if you close the contact)
1 = NC (the input will be active if you open the contact)
2 = input not enabled
i2
-1
120
min
30
delay before the door switch alarm is activated
-1 = no signal
i3
-1
120
min
15
maximum duration of the effect provoked by the activation of the door switch input
-1 = the effect will last as long as the input will be deactivated
i5
0
6
—
3
effect provoked by the activation of the multipurpose input
0 = no effect
1 =
SYNCHRONIZING THE dEFROSTS
- after time d5, the defrost will be activated
2 =
ACTIVATING ENERGY SAVING
- Energy Saving function will be activated (until
the input is deactivated); also look at r4
3 =
ACTIVATING THE EXTERNAL ALARM
- after time i7, the display will flash the
code
“iA”
and the buzzer will be activated (until the input is deactivated)
4 =
ACTIVATING THE COMPRESSOR LOCKOUT
- the compressor will be turned
off, the display will flash the code
“iA”
and the buzzer will be activated (until the
input is deactivated); also look at i7, i8 and i9
5 =
TURNING OFF THE CONTROLLER
- the controller will be turned off via software
(until the input is deactivated); also look at C0, d4 and A6
6 =
ACTIVATE COOLING
(only PSK223 and PSK233) - the compressor will be turned
on (until the input is deactivated); in this case parameters C4 and C5 are not
meaningful
Temperature Alarms