Parker Sporlan PSK Series Скачать руководство пользователя страница 26

Page 2 

– Bulletin 100-50-6.4

2  USER INTERFACE

2.1  Introductory comments
The device has the following operational states:
•  “on” (power is connected and the controller is on: the regulators 

may be switched on)

•  “stand-by” (power is connected but software sets the controller to 

off: the regulators are switched off; the option of manually switch-
ing on/off the cabinet light or the auxiliary output depends on 
parameter u2).

The term “turning on” is understood to mean switching from the 
stand-by state to on; the term “turning off” is understood to mean 
switching from the on state to the stand-by state.
When the controller is turned on, it restores the state it was in when 
power was interrupted.

2.2  Manual switching on/off of the controller
•  make sure the keyboard is not locked and no procedure is running
•  press and hold    for 4 seconds.
It is also possible to turn the controller on/off using the multifunction 
input.

2.3  The display

If the controller is turned on, during normal operation the display 
will show the quantity you have set with parameter P5.
While in stand-by mode the display is turned off.

2.4  Showing the temperature read by the probes
•  make sure the keyboard is not locked and no procedure is running
•  press and hold 

 for 2 seconds: the display will show the first 

available label

•  press 

 or 

  to select “

Pb1” (cabinet probe), “Pb2” (evaporator 

probe), or “

Pb3” (auxiliary probe) 

•  press 
To quit the procedure:
•  press 

  or do not press any other buttons for 60 seconds

•  press 

 or 

 as long as the display shows the quantity you have 

set with parameter P5 or do not press any other buttons for 60 
seconds.

Alternatively:
•  press 
If there is no evaporator probe (parameter P3 = 0), label “

Pb2” will 

not be shown.
If the function of the fourth input is not for an auxiliary probe (pa-
rameter P4 = 0 or 3), then label “

Pb3” will not be shown.

2.5  Manually activating defrost
•  make sure the keyboard is not locked and no procedure is running
•  press and hold 

 for 4 seconds.

If the function of the evaporator probe is set for a defrost probe 
(parameter P3 = 1) and the evaporator temperature is above that 
established by parameter d2, then defrost will not be activated.

2.6  Manually turning on/off the cabinet light 

(only if parameter u1 is set to 0)

•  make sure no procedures are running
•  press 
It is also possible to turn the cabinet light on/off remotely using the 
microport and multifunction inputs; see also parameter u2.

2.7  Manually turning on the anti-sweat heater 

(only if parameter u1 is set to 1)

•  make sure the controller is turned on and no procedures are running
•  press 

 for 2 seconds: the anti-sweat heater will be turned on for 

the period of time established by parameter u6.

Manually turning off of the anti-sweat heater is not permitted.

2.8  Manually turning on/off the auxiliary output 

(only if parameter u1 is set to 2)

•  make sure the keyboard is not locked and no procedure is running
•  press 
It is also possible to turn the auxiliary output on/off using the multi-
function input.
The auxiliary output can be turned off manually by the same process 
in section 2.8, only if it was turned on manually (the same applies for 
remotely turning on the auxiliary output); see also parameter u2.

2.9  Locking/unlocking the keyboard
To lock the keyboard:
•  make sure no procedures are running
•  press and hold 

 and 

 for 2 seconds: the display will show 

Loc” for 1 second.

If the keyboard is locked, it will not be possible to:
•  manually turn the device on/off
•  show the temperature read by the cabinet probe, evaporator probe, 

or auxiliary probe (using the procedure indicated in paragraph 2.4)

•  manually activate defrost
•  manually turn the auxiliary output on/off
•  view information pertaining to the HACCP alarms
•  delete the HACCP alarm list
•  change the operational setpoint using the procedure indicated in 

paragraph 3.1

•  display the total hours of compressor operation
•  delete the total hours of compressor operation.
These operations will cause the label “

Loc” to be displayed for 1 

second.
To unlock the keyboard:
•  press and hold 

 and 

 for 2 seconds: the display will show 

UnL” for 1 second.

3 SETTINGS

3.1  Setting the working setpoint
•  make sure the keyboard is not locked and no procedure is running
•  press 

: LED   will flash

•  press 

 or 

 within 15 seconds; also see parameters r1, r2 and r3

•  press 

 or do not press any other button for 15 seconds.

You also can modify the working setpoint through parameter SP.

3.2  Setting the configuration parameters
To gain access to the procedure:
•  make sure no procedures are running
•  press and hold 

 and 

 for 4 seconds: the display will show “

PA

•  press 
•  press 

 or 

 within 15 seconds to set the display to “

-19

•  press 

 or do not press any other button for 15 seconds

Содержание Sporlan PSK Series

Страница 1: ...PSK Series Refrigeration Controllers For Low and Medium Temperature Applications...

Страница 2: ...with the PSK201 with simple logic and wiring for base compressor and defrost control to the PSK214 with multiple I Os and evaporator fan management for complex compressor defrost and fan control A qui...

Страница 3: ...st and auxiliary light anti sweat heater etc HACCP compliant data logging Available with 3 4 inputs Real Time Clock RTC for added control All models are UL and CE approved Easy to read 3 1 2 digit dis...

Страница 4: ...ature probe e g condenser over heat sensor a door switch a second door switch on the 204 and 214 models or as a digital input The digital input can be used to synchronize defrosts activate energy savi...

Страница 5: ...K201 according to safety regulations protection against access to electrical parts must be ensured by a correct installation of the controller the parts that ensure this protection must be installed s...

Страница 6: ...r Make sure the default value of the parameters is correct in particular note if the probes are PTC probes 4 SIGNALS 4 1 Signals LED EXPLANATION LED compressor if lit the compressor will be turned on...

Страница 7: ...setpoint r2 r1 99 0 C F 50 0 maximum working setpoint Parameters Minimum Maximum U M PSK201 Compressor Protections C0 0 240 min 0 compressor delay after turning on the controller C2 0 240 min 3 minimu...

Страница 8: ...final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the...

Страница 9: ...nches is the maximum depth with screw terminal blocks 83 0 mm 3 267 inches is the maximum depth with extractable terminal blocks the panel thickness must not be greater than 8 0 mm 0 314 in working co...

Страница 10: ...but do not hold any button pressing any button without holding it will not initiate the normal command for that button 3 SETTINGS 3 1 Setting the working setpoint make sure the keyboard is not locked...

Страница 11: ...mperature Inputs CA1 25 0 25 0 C F 0 0 cabinet probe offset CA2 25 0 25 0 C F 0 0 evaporator probe offset P0 0 1 1 kind of probe 0 PTC 1 NTC P1 0 1 1 display decimal point value during norman operatio...

Страница 12: ...remains turned on during the cabinet probe error also look at C4 Parameters Minimum Maximum U M DEF Defrost d0 0 99 h 8 defrost interval also look at d8 0 the defrost at intervals will never be activa...

Страница 13: ...ameters Minimum Maximum U M DEF Digital Inputs Only PSK223 and PSK233 i0 0 3 2 kind of digital input 0 MULTIPURPOSE INPUT in this case look at parameters i1 i5 i7 i8 and i9 1 RESERVED 2 DOOR SWITCH IN...

Страница 14: ...cked alarm only if i5 4 0 alarm not enabled i9 1 999 min 240 time without multipurpose input alarms such as to provoke the alarm counter to be cleared only if i5 4 Parameters Minimum Maximum U M DEF S...

Страница 15: ......

Страница 16: ...final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the...

Страница 17: ...17 Electrical Connection PSK221 electric system second input P4 1 or 2 P4 3 1 2 3 4 5 10 12 11 10 12 11 K1 power supply comp cabinet cabinet auxiliary multip door switch max 10 A PSK221 serial port el...

Страница 18: ...second If the keyboard is locked you will not be allowed to show the temperature read by the auxiliary probe activate defrost by hand modify the working setpoint with the procedure related in paragrap...

Страница 19: ...imum U M DEF Working Setpoints r1 r2 C F 0 0 working setpoints Parameters Minimum Maximum U M DEF Working Setpoints SP r1 r2 C F 0 0 working setpoints Parameters Minimum Maximum U M DEF Temperature In...

Страница 20: ...is activated only if P4 2 C7 0 0 199 0 C F 90 0 condenser temperature above which the compressor locked alarm is activated only if P4 2 C8 0 15 min 1 compressor locked alarm delay only if P4 2 Parame...

Страница 21: ...min 15 high temperature alarm delay since the deactivation of the door switch input only if P4 3 and i0 3 Parameters Minimum Maximum U M DEF Digital Inputs Only if P4 3 i0 0 3 3 kind of digital input...

Страница 22: ......

Страница 23: ......

Страница 24: ...final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the...

Страница 25: ...nches mm inches A 71 0 2 79 71 0 2 79 71 8 2 82 B 29 0 1 14 29 0 1 14 29 8 1 17 Electrical Connection PSK204 the parts that ensure this protection must be installed so that they can not be removed wit...

Страница 26: ...sure no procedures are running press It is also possible to turn the cabinet light on off remotely using the microport and multifunction inputs see also parameter u2 2 7 Manually turning on the anti...

Страница 27: ...e alarms on condition that the critical value is more critical than the one the instrument has stored or on condition that the information has already been displayed no alarms will be recorded if the...

Страница 28: ...atively press 5 3 Resetting the compressor operation time make sure the keyboard is not locked and no procedure is running press and hold for 2 seconds the display will show the first available label...

Страница 29: ...1 kind of probe 0 PTC 1 NTC P1 0 1 1 display decimal point value during normal operation Celsius mode only 1 YES P2 0 1 0 unit of measure temperature 0 C 1 F P3 0 2 1 evaporator probe function 0 probe...

Страница 30: ...the activation of defrost the cabinet temperature is above working setpoint r0 at most the current cabinet temperature d7 0 15 min 2 drip delay d8 0 2 0 kind of defrost interval 0 the defrost will be...

Страница 31: ...he input will be active if you open the contact i2 1 120 min 30 microport input alarm signal delay 1 the alarm will not be reported i3 1 120 min 15 maximum duration of the effect caused by activation...

Страница 32: ...ve is deactivated in relation to the operational setpoint i e the operational setpoint u7 only if u1 6 u8 0 1 0 evaporator valve contact type only if u1 6 0 NO valve active with contact closed 1 NC va...

Страница 33: ...B 29 0 1 14 29 0 1 14 29 8 1 17 Electrical Connection PSK214 the parts that ensure this protection must be installed so that they can not be removed without the use of a tool 1 3 Wiring diagram With...

Страница 34: ...hold for 2 seconds the display will show the first available label press or to select Pb2 press To quit the procedure press or do not press any other buttons for 60 seconds press or as long as the di...

Страница 35: ...iated effect If the fourth output is set as an alarm output parameter u1 4 and parameter u4 is set to 1 then silencing the alarm buzzer will also deactivate the alarm output 3 SETTINGS 3 1 Setting the...

Страница 36: ...er following the code the older the alarm To select an alarm press or to select AH3 for example To display the information relating to the alarm press HACCP LED will stop flashing and remain on and th...

Страница 37: ...C2 and i7 LED defrost if lit defrost is running if flashing defrosting has been requested but compressor protection is ongoing parameters C0 C1 and C2 the device is waiting for the drip delay to comp...

Страница 38: ...temperature increase during Energy Saving function only if P4 3 and i5 2 or 3 refer also to HE1 and HE2 Parameters Minimum Maximum U M DEF Compressor Protections C0 0 240 min 0 compressor delay after...

Страница 39: ...setpoint r0 at most the current cabinet temperature d7 0 15 min 2 drip delay d8 0 3 0 kind of defrost interval 0 PERIODIC the defrost will be activated when the controller has remained turned on for...

Страница 40: ...if you close the contact 1 NC the input will be active if you open the contact i2 1 120 min 30 microport input alarm signal delay 1 the alarm will not be reported i3 1 120 min 15 maximum duration of...

Страница 41: ...ced only if u1 4 1 YES u5 99 99 C F 1 cabinet temperature above which the door element is switched off only if u1 5 u6 1 120 min 5 anti sweat heater duration only if u1 1 u7 0 99 C F 2 cabinet tempera...

Страница 42: ......

Страница 43: ......

Страница 44: ...final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the...

Отзывы: