9

4. Operation 

4.1 Start-up Checks 

4.1.1  Installing  Components                                                                                                                    

If unicells and filter media were removed for shipment or 
installation, refer to Figure 6 for proper installation and electrical 
contact alignment. Filter media is installed as after filters (after 
the unicell) with In Place Cleaning. Do not install filter media 
as pre filters (before the unicell) with In Place Cleaning. This 
will reduce the effectiveness of the wash cycle by 50 percent. 
The filter media is utilized as pre and after filters if the PSG is 
not equipped with In Place Cleaning. The PSG inlet plenum, if 
supplied by Parker, will have baffle filters or aluminum media.  
The inlet plenum should be inspected that all baffle filters or 
aluminum filters are installed.  

4.1.2  Ducting  Connections                                                                                                                  

Blower speeds are factory set by the blower manufacturer to 
compensate for static pressure losses in ducting as specified 
by others. Starting the blower before ducting is complete or 
before debris is removed can result in motor overload or other 
system damage. 

4.1.3 Blower Rotation                                                                                                                   

For proper airflow, the blower should be operating in the correct 
direction. If the blower is operating in the reverse direction, air 
will move in the proper direction, but at significantly reduced 
rates. To check rotation: 

1. Place PSG unit off line. 

2.  Remove blower housing from the blower to observe the 

pulley rotation. 

3.  Place the PSG unit on line for approximately one minute. 

4. Place PSG unit off line. 

5.  As the blower pulley slows down, observe the direction of 

rotation. 

6.  Note directional arrow located on the blower housing. 

 

Extreme care should be exercised when operating 
blowers with motor/drive belts exposed. Loose 
fitting clothing can easily be drawn into these 
moving parts.

   7.  If blower wheel was not rotating in the correct direction, 

disengage main three-phase fused disconnect switch. 

Do not attempt to rewire “live” electrical connections. 

8.  Open power panel and reverse any two of the three wires 

at the terminal strip (Ll, L2, and L3). 

   9.  Engage the main three phase fused disconnect switch and 

place the PSG on line, checking blower rotation. 

!

 WARNING

!

 WARNING

4.1.4 Blower Belt Tension  

The drive belt tension adjustment is critical within the first 24 
hours of the system exhaust blower operation. During this 24 
hour period, the initial stretch of the belt occurs which requires 
a belt tension adjustment. If this tension adjustment is not 
completed the belt will wear prematurely, requiring a  replacement. A 
drive belt tension gage should be used for adjusting belt tension. If 
fan belt tension is improper, set tension by adjusting the motor slide 
base. Loosen four bolts holding the motor to the base and turn the 
adjustment bolt(s) on the base. Check with a steel straight edge to 
make sure that motor pulley and blower pulley is still aligned. Tighten 
motor mounting bolts. Figure 7 illustrates a typical motor/blower 
arrangement (motor/blower configurations will vary). 

  

  

Improper tension on drive belts will cause premature 
failure of belts. 

4.1.5 Blower Current Measurement 

Using an ammeter measure the current amperage of the blower 
motor. The measurement should not exceed the full load ampere 
(FLA) rating identified on the blower motor nameplate. If the over-
load relay is tripping perform the following: check overload relay 
for proper setting per motor FLA, measure blower rpm and design 
static pressure to determine that actual conditions are per blower 
specifications. Blower rpm can be measured with a tachometer. 
Design or total static pressure (TSP) is the summation in static pres-
sure between the blower inlet and outlet. This summation is best 
checked with a manometer and pitot tube measuring readings from 
(a) the exhaust transition near the blower inlet and (b) the exhaust 
stack after the blower outlet. If the actual static pressure is higher 
than the blower specifications, and or the blower rpm is higher than 
the blower specifications, reduce the blower speed by opening the 
variable pitch pulley as described in the next procedure. Blower 
specifications or blower curve refers to the established operating 
conditions set by the blower manufacturer, rpm, cfm (air volume), 
and TSP. A reduction in blower rpm will decrease the TSP. A new 
pulley set may be required to reduce the blower rpm and amperage. 
The blower can be supplied either by Parker or by others. A blower 
curve can be requested through the blower manufacturer with the 
serial number. 

Figure 7

Typical Motor/Blower Configuration

  CAUTION

Содержание SMOG-HOG PSG

Страница 1: ...SMOG HOG Electrostatic Air Cleaner Owner s Manual Model PSG...

Страница 2: ...ion avail able when contacting Parker Parker Order _________________________________________________________________ Unit Model ___________________________________________________________________ Unit...

Страница 3: ...2 3 Supports 3 2 3 1 Skidded Systems 3 2 3 2 Unskidded Systems 3 2 3 3 Utilities Drains 3 2 3 4 Ducting 3 3 Installation 4 3 1 Receiving Inspection 4 3 2 Unloading by Forklift 4 3 3 Unloading by Cran...

Страница 4: ...eck Power Pack Enclosure Indicator Light s 12 5 1 2 Unicell s Weekly Visual Inspection 12 5 1 3 Filters Drain Sumps and Access Door Gasket Inspection 12 5 1 4 Perform An In Place Cleaning Wash Cycle 1...

Страница 5: ...1 Tools Required 17 10 2 Perform Before Troubleshooting 17 10 3 Troubleshooting Procedure 17 10 4 Step 1 Checking the Power Pack 18 10 5 Step 2 Checking the Unicell Components 19 10 6 High Voltage Pr...

Страница 6: ...explosive Use non flammable cleaners Keep flammable materials and vapors such as gasoline away from unit The unit should be inspected frequently and contaminants removed to prevent excessive accumula...

Страница 7: ...ims any liability or responsibility for damage from fires or explosions regardless of origin Parker recommends that all APC dust collection equipment installation and application conform to any and al...

Страница 8: ...h is non lethal Unicell components are usually preceded and or followed by mesh filters to assure even distribution of air at low velocity Air movement is provided by a system blower located behind th...

Страница 9: ...r pack is self protecting against overloads e g dirty components short circuits in ionizer and cell circuits and is self regulating when the AC voltage supply varies from 90 to 132 VAC 1 4 2 Unicell I...

Страница 10: ...ng are general guidelines 2 1 Location Systems should be located as near as possible to the emission source but with consideration given to utility proximity and safe maintenance access Indoor locatio...

Страница 11: ...led by forklift truck but final placement may require a crane refer to unit System Layout Drawing for weights sizes and notes detailing responsibilities of the installing contractor 3 2 Unloading By F...

Страница 12: ...tem Installation If PSG installation is delayed for an extended period one month or more protect system components as follows 1 Store in a cool dry location Do not disassemble Do not re move component...

Страница 13: ...procedure until a 1 4 clearance is obtained between top place and housing 3 Check the level of the equipment The equipment may now be leveled by making small adjustments of individual isolators at the...

Страница 14: ...rmed by a qualified electrician in accordance with local electrical codes Disconnect electrical power before installing or servicing electrical components The PSG is manufactured per job specification...

Страница 15: ...ZER CELL FEED THRU INSULATOR ASSEMBLIES 2 37 0026 INSULATOR ONLY 2 6 37 0028 IONIZER STANDOFF INSULATOR 4 7 03 0559 IONIZER WIRE SPRING 20 8 03 0738 IONIZER WIRE 10 MIL SST 10 9 30 0387 CELL CONTACT S...

Страница 16: ...Tension The drive belt tension adjustment is critical within the first 24 hours of the system exhaust blower operation During this 24 hour period the initial stretch of the belt occurs which requires...

Страница 17: ...peed will decrease airflow CFM and current amperage To decrease speed open the variable pitch pulley from normal as in Figure 8A toward full open as in Figure 8C To adjust the variable pitch pulley 1...

Страница 18: ...media which does not support combustion PSG systems requiring an ETL listing will have potassium permanganate The odor control cabinet consists of a number of odor filters as dictated by size of the...

Страница 19: ...us panel or remote beacon or BMS Occasional arcing flashing of an indicator light is normal An established arcing condition or dead short condition continuous flashing of an indicator light or the ind...

Страница 20: ...etergent concentration in a mixture with water varies with the application from 1 1 to 25 1 parts water to parts detergent For any contaminant condition the best course is to use a cleaning solution p...

Страница 21: ...cement set of unicells and filter media 7 3 Automatic Parts Washers Certain commercially available units which are effective combine and automate the features necessary for effective cleaning includin...

Страница 22: ...l the replacement indicator light reversing the procedure 9 4 Component Access Door s Gasket Replacement Should leakage occur an adjustment of the latch paws on the back of the door handles may solve...

Страница 23: ...en power pack enclosure lid cover 3 3 Loosen 5 16 hex jam nut 9 then back off push rod extension 1 to end of threads 4 Close power pack enclosure lid cover listening for point where limit switch 4 is...

Страница 24: ...will decrease collection efficiency 2 There are run away voltages to the power pack requiring power pack replacement above 12 0 KVDC to the ionizer circuit and 7 5 KVDC to the collector cell circuit...

Страница 25: ...itch in the on position and engage the interlock switch Confirm 120 VAC to the power pack enclosure terminals not the power pack terminals 5 and 6 Verify the interlock switch operation 120 VAC to the...

Страница 26: ...igh voltage feed through insulator replace insulator Ionizer wires not taut contacting the ground plates Bent ionizer wire support bar contacting a grounded surface Bent ground plates contacting the i...

Страница 27: ...all outlet 6 Measure high voltage with the high voltage probe ionizer volt age should be 10 0 to 11 8 KVDC not to exceed 12 0 KVDC If ionizer voltage exceeds 12 0 KVDC the ionizer wires are moderately...

Страница 28: ...e 5 0 to 7 5 KVDC not to exceed 7 5 KVDC The collector cell will not maintain high voltages above 7 5 KVDC The collector cell will continuously arc Usually this condition is caused by a power pack abo...

Страница 29: ...ure indicator light is not illuminated Power pack enclosure toggle switch is in the off position Remove debris Power pack enclosure s push rod assembly is not properly adjusted Refer to Section 9 5 Po...

Страница 30: ...y 1 Unit Model Number nameplate 2 Unit Serial Number 3 Part Number or Part Description see illustrated parts 11 2 Returning Parts When returning parts directly to Parker call Customer Service at 1 800...

Страница 31: ...24 12 Power Pack Enclosure Assembly 16 17 12 13 15 35 4 28 26 29 34 19 22 18 24 25 23 1 20 21 31 30 27 31 1 32 33 8 1 5 7 6 2 3 9 10 11 14 POWER PACK ENCLOSURE ILLUSTRATION...

Страница 32: ...eed Through Insulator 2 19 30 0398 Round Head Screw 10 32 x 4 SST 2 20 30 0412 Lock Washer 10 EXT Tooth SST 2 21 30 0367 Fender Washer x 1 1 2 SST 2 22 35 0013 Spacer 2 23 30 0310 Pal Nut 5 8 16 2 24...

Страница 33: ...ced if necessary by the manufacturer trained and or certified agent A record of such inspection and cleaning shall be kept on the premises for inspection 7 Certificate of Approval number shall be plai...

Страница 34: ...or misuse misapplication or normal wear and tear e Equipment not properly installed operated and maintained under normal conditions and recommended applications As Buyers exclusive remedy for any def...

Страница 35: ...shooting effort details 5 Description of physical location and or environment details The Buyer shall cooperate with PARKER in its investigation and provide full information and documentation concerni...

Страница 36: ...rlands 31 76 508 5300 www parker com dhfns Hiross Zander Essen Germany 49 2054 9340 www parker com hzfd Padova Italy 39 049 9712 111 www parker com hzfd Engine Filtration Water Purification Racor Dews...

Отзывы: