isysNet 24 VDC Output Modules, Series A 

E107P

5

Make sure all connectors and caps are securely tightened to 
properly seal the connections against leaks and maintain IP67 
requirements.

!

ATTENTION

PSST16M23A

PSST16D25A

Communicate With Your Module

I/O messages are sent to (consumed) and received from (produced) 
the I/O modules. These messages are mapped into the processor’s 
memory.   These  I/O  output  modules  produce  1  or  2  bytes  of  input 
data (scanner Rx - status).  They consume 1 or 2 bytes of I/O data 
(scanner Tx).
Default Data Map for the Output Modules 
PSST8M23A, PSST8M12A, PSST8M8A
Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produces 0 

(Scanner Rx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

Channel

Status

Produces 1 Ch15 Ch14 Ch13 Ch12 Ch11 Ch10 Ch9 Ch8 Channel

Status

Consumes 0 

(Scanner Tx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

Output 

State

Consumes 1 Ch15 Ch14 Ch13 Ch12 Ch11 Ch10 Ch9 Ch8 Output 

State

Where: Channel Status 0 = no error, 1 = error;

 

Output State 0 = OFF, 1 = ON

7

6

5

4

3

2

1

0

Produces 

(Scanner Rx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

Channel

Status

Consumes 0 

(Scanner Rx) Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0

Output 

State

Where: Channel Status 0 = no error, 1 = error;

 

Output State 0 = OFF, 1 = ON

EDS File Requirements

The EDS files are available online at www.parker.com/pneu/isysnet.

PSST16M23A, PSST16D25A, PSST16M12A
Message Size: 2 Byte

   13 
  12 
  11 
  10 
 

9

 

8

 

7

 

6

 

5

 

4

 

3

 

2

 

1

  25 
  24 
  24 
  22 
  21
  20
  19
  18
  17
  16
  15
  14

Pin

Number

Pin

Number

D-Sub, 25-Pin Female Connector

Pin

Description

Function

Remarks

1

Channel 0 Output

Output

24VDC @500mA

2

Channel 2 Output

Output

24VDC @500mA

3

Channel 4 Output

Output

24VDC @500mA

4

Channel 6 Output

Output

24VDC @500mA

5

Channel 8 Output

Output

24VDC @500mA

6

Channel 10 Output

Output

24VDC @500mA

7

Channel 12 Output

Output

24VDC @500mA

8

Channel 14 Output

Output

24VDC @500mA

9

24VDC Common

Common

24VDC Return

10

24VDC Common

Common

24VDC Return

11

24VDC Common

Common

24VDC Return

12

24VDC Common

Common

24VDC Return

13

24VDC Common

Common

24VDC Return

14

Channel 1 Output

Output

24VDC @500mA

15

Channel 3 Output

Output

24VDC @500mA

16

Channel 5 Output

Output

24VDC @500mA

17

Channel 7 Output

Output

24VDC @500mA

18

Channel 9 Output

Output

24VDC @500mA

19

Channel 11 Output

Output

24VDC @500mA

20

Channel 13 Output

Output

24VDC @500mA

21

Channel 15 Output

Output

24VDC @500mA

22

24VDC Common

Common

24VDC Return

23

24VDC Common

Common

24VDC Return

24

24VDC Common

Common

24VDC Return

25

24VDC Common

Common

24VDC Return

M23, 19-Pin Female Connector

Pin

Description

Function

Remarks

1

Channel 0 Output

Output

24VDC @500mA

2

Channel 1 Output

Output

24VDC @500mA

3

Channel 2 Output

Output

24VDC @500mA

4

Channel 3 Output

Output

24VDC @500mA

5

Channel 4 Output

Output

24VDC @500mA

6

24VDC Common

Common

24VDC Return

7

Channel 5 Output

Output

24VDC @500mA

8

Channel 6 Output

Output

24VDC @500mA

9

Channel 7 Output

Output

24VDC @500mA

10

Channel 8 Output

Output

24VDC @500mA

11

Channel 9 Output

Output

24VDC @500mA

12

Not Used

13

Channel 10 Output

Output

24VDC @500mA

14

Channel 11 Output

Output

24VDC @500mA

15

Channel 12 Output

Output

24VDC @500mA

16

Channel 13 Output

Output

24VDC @500mA

17

Channel 14 Output

Output

24VDC @500mA

18

Channel 15 Output

Output

24VDC @500mA

19

Not Used

11

5

4

3

2

1

10

19

12

6

7

8

9

13

14

15

16

17

18

Содержание PSST8M23A

Страница 1: ...uct or systems in the current product catalog Due to the variety of operating conditions and applications for these products or systems the user through its own analysis and testing is solely responsible for making the final selection of the products and systems and assuring that all performance safety and warning requirements of the application are met The products described herein including with...

Страница 2: ...en not in use store the equipment in appropriate static safe packaging ATTENTION Environment and Enclosure This equipment is intended for use in overvoltage Category II applications as defined in IEC publication 60664 1 at altitudes up to 2000 meters without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precauti...

Страница 3: ... 60 7 3 02 76 6 3 13 79 4 5 98 151 9 0 87 22 Drill and Tap for M6 Screw Ground Lug Connection Latching Mechanism Mounting Base Keyswitch Set to position 1 for the PSST8M digital output modules Install the Mounting Base as Follows 1 Lay out the required points as shown above in the drilling dimension drawing 2 Drill the necessary holes for 8 M4 machine or self tapping screws 3 Mount the base using ...

Страница 4: ...7 PSST8M12A 24V dc Out 0 1 2 3 4 5 6 7 Module Will Bridge Two Bases Wire the Output Modules Following are wiring instructions for the digital output modules view into connector Pin 1 Output 0 Pin 7 Output 6 Pin 2 Output 1 Pin 8 Output 7 Pin 3 Output 2 Pin 9 Return Com Pin 4 Output 3 Pin 10 Return Com Pin 5 Output 4 Pin 11 24VDC Pin 6 Output 5 Pin 12 Chassis 8 5 4 11 3 2 10 12 6 1 9 7 PSST8M23A vie...

Страница 5: ... 2 Output Output 24VDC 500mA 3 Channel 4 Output Output 24VDC 500mA 4 Channel 6 Output Output 24VDC 500mA 5 Channel 8 Output Output 24VDC 500mA 6 Channel 10 Output Output 24VDC 500mA 7 Channel 12 Output Output 24VDC 500mA 8 Channel 14 Output Output 24VDC 500mA 9 24VDC Common Common 24VDC Return 10 24VDC Common Common 24VDC Return 11 24VDC Common Common 24VDC Return 12 24VDC Common Common 24VDC Retu...

Страница 6: ...that the PSST8M12A is now under the I O configuration Add 24 VDC Output Modules to RSLogix 5000 I O Configuration To add your output modules to RSLogix 5000 I O configuration follow these steps In RSLogix 5000 For ControlNet highlight the PSSCCNA or 1738 ACNR Shown right click and select New Module For EtherNet IP highlight the PSSCENA or 1738 AENT Shown right click and select New Module ...

Страница 7: ... active and under control Flashing Red Open circuit detection No load Off State only Red Short circuit detected On State only Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing incomplete or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable fault may require device re...

Страница 8: ... IEC 60068 2 2 Test Bb Un packaged Non operating Dry Heat 40 to 85 C 40 to 185 F Relative Humidity IEC 60068 2 30 Test Db Un packaged Non operating Damp Heat 5 to 95 Non condensing Shock IEC60068 2 27 Test Ea Unpackaged Shock Operating 30g Non operating 50g Vibration IEC60068 2 6 Test Fc Operating 5g 10 to 500Hz ESD Immunity IEC 61000 4 2 6kV Contact Discharges 8kV Air Discharges Radiated RF Immun...

Отзывы: