background image

isysNet 24 VDC Output Modules, Series A 

E107P

8

Digital Output Modules
Outputs per Module

8 (1 Group of 8) Non-isolated, Sourcing

16 (1 Group of 16) Non-isolated, Sourcing

Voltage Drop, On-State Output, Maximum

0.2VDC (Sourcing Modules) 
0.7VDC (Sinking Module)

Voltage, Off-State Output, Maximum

28.8VDC 

Voltage, On-State Output, 
Maximum
Minimum
Nominal

28.8VDC
10VDC
24VDC

Current Leakage, Off-State Output, Maximum

0.5 mA

Current, On-State Output Minimum

1.0 mA Per C hannel

Output Current Rating

1.0 A Per Channel, Not To Exceed 3.0 A Maximum Per Module

Output Delay Time OFF to ON, Maximum

1

0.1 ms

Output Delay Time, ON to OFF, Maximum

1

0.1 ms

Output Point Density

8 or 16

Output Surge Current, Maximum

2 A for 10 ms, Repeatable Every 3 Seconds

External DC Power Supply Current

32 mA 

External DC Power Supply Voltage Range

10 to 28.8VDC

External DC Power Supply Voltage Nominal

24VDC

Keyswitch Position

1

LED Indicators

8 orr 16 Yellow/Red Output Status, Logic Side
1 Green/Red Network Status, Logic Side
1 Green/Red Module Status, Logic Side

PointBus Current, Maximum

75 mA @ 5VDC

Power Dissipation, Maximum

PSST8M - 2.0W @ 28.8VDC 

Thermal Dissipation, Maximum

PSST8M - 6.8 BTU/hr. @ 28.8VDC

Isolation Voltage
(continuous-voltage withstand rating)

50V rms
Tested at 1250VAC rms for 60s

Dimensions (includes I/O module                Inches
and mounting base)                             (Millimeters)

4.72H x 2.82W x 1.65D
(120H x 72W x 42D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% Non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):
5g @ 10 to 500Hz

ESD Immunity

IEC 61000-4-2:
6kV Contact Discharges
8kV Air Discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz Sine-wave 80% AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100% AM at 900Mhz
10V/m with 200Hz 50% Pulse 100% AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:  ±3kV at 5kHz on Signal Ports

Surge Transient Immunity

IEC 61000-4-5:  ±1kV Line-line(DM) and ±2kV Line-earth(CM) on Signal Ports

Conducted RF Immunity

IEC 61000-4-6:  10Vrms with 1kHz Sine-wave 80%AM from 150kHz to 80MHz

Emissions

CSPR 11:  Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque

#8 Screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

2

1 - on Signal Ports

Weight Imperial (Metric)

0.64 lb. (0.29 kg)

Certifications:
(when product is marked)

c-UL-us

UL Listed Industrial Control Equipment, 
certified for US and Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity

C- Tick

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; 
Industrial Emissions

1. OFF to ON or ON to OFF delay is time from a valid output “on” or “off” signal to output energization or de-energization.
2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.

      

Specifications - 

Following are specifications for the digital output modules.

Содержание PSST8M23A

Страница 1: ...uct or systems in the current product catalog Due to the variety of operating conditions and applications for these products or systems the user through its own analysis and testing is solely responsible for making the final selection of the products and systems and assuring that all performance safety and warning requirements of the application are met The products described herein including with...

Страница 2: ...en not in use store the equipment in appropriate static safe packaging ATTENTION Environment and Enclosure This equipment is intended for use in overvoltage Category II applications as defined in IEC publication 60664 1 at altitudes up to 2000 meters without derating This equipment is considered Group 1 Class A industrial equipment according to IEC CISPR Publication 11 Without appropriate precauti...

Страница 3: ... 60 7 3 02 76 6 3 13 79 4 5 98 151 9 0 87 22 Drill and Tap for M6 Screw Ground Lug Connection Latching Mechanism Mounting Base Keyswitch Set to position 1 for the PSST8M digital output modules Install the Mounting Base as Follows 1 Lay out the required points as shown above in the drilling dimension drawing 2 Drill the necessary holes for 8 M4 machine or self tapping screws 3 Mount the base using ...

Страница 4: ...7 PSST8M12A 24V dc Out 0 1 2 3 4 5 6 7 Module Will Bridge Two Bases Wire the Output Modules Following are wiring instructions for the digital output modules view into connector Pin 1 Output 0 Pin 7 Output 6 Pin 2 Output 1 Pin 8 Output 7 Pin 3 Output 2 Pin 9 Return Com Pin 4 Output 3 Pin 10 Return Com Pin 5 Output 4 Pin 11 24VDC Pin 6 Output 5 Pin 12 Chassis 8 5 4 11 3 2 10 12 6 1 9 7 PSST8M23A vie...

Страница 5: ... 2 Output Output 24VDC 500mA 3 Channel 4 Output Output 24VDC 500mA 4 Channel 6 Output Output 24VDC 500mA 5 Channel 8 Output Output 24VDC 500mA 6 Channel 10 Output Output 24VDC 500mA 7 Channel 12 Output Output 24VDC 500mA 8 Channel 14 Output Output 24VDC 500mA 9 24VDC Common Common 24VDC Return 10 24VDC Common Common 24VDC Return 11 24VDC Common Common 24VDC Return 12 24VDC Common Common 24VDC Retu...

Страница 6: ...that the PSST8M12A is now under the I O configuration Add 24 VDC Output Modules to RSLogix 5000 I O Configuration To add your output modules to RSLogix 5000 I O configuration follow these steps In RSLogix 5000 For ControlNet highlight the PSSCCNA or 1738 ACNR Shown right click and select New Module For EtherNet IP highlight the PSSCENA or 1738 AENT Shown right click and select New Module ...

Страница 7: ... active and under control Flashing Red Open circuit detection No load Off State only Red Short circuit detected On State only Indication Probable Cause Module Status Off No power applied to device Green Device operating normally Flashing Green Device needs commissioning due to missing incomplete or incorrect configuration Flashing Red Recoverable fault Red Unrecoverable fault may require device re...

Страница 8: ... IEC 60068 2 2 Test Bb Un packaged Non operating Dry Heat 40 to 85 C 40 to 185 F Relative Humidity IEC 60068 2 30 Test Db Un packaged Non operating Damp Heat 5 to 95 Non condensing Shock IEC60068 2 27 Test Ea Unpackaged Shock Operating 30g Non operating 50g Vibration IEC60068 2 6 Test Fc Operating 5g 10 to 500Hz ESD Immunity IEC 61000 4 2 6kV Contact Discharges 8kV Air Discharges Radiated RF Immun...

Отзывы: