192-011006N8 PSD1 Installation Guide
192-011006N8 2019-07
09.10.19 09:27
97 (109)
8.2.3.
Mains Connection Power module PSD1-M_P020 without line choke
Category
Specifications
PSD1-M_P020
230 V
400 V
480 V
Mains voltage
230 VAC ±10 % 50-60 Hz
400 VAC ±10 % 50-60 Hz
480VAC ±10% 50-60Hz
Rated voltage
3 AC 230 V
3 AC 400 V
3 AC 480 V
Input Current
44 Arms
44 Arms
35 Arms
Output voltage
325 VDC ±10 %
565 VDC ±10 %
680 VDC ±10 %
Output power
12 kW
20 kW
20 kW
Pulse power (<5 s)
24 kW
40 kW
40 kW
Power dissipation
120 W
120 W
120 W
Maximum fuse rating per
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC (depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
8.2.4.
Mains connection Power module PSD1-M_P020 with line choke
Increased power by means of a line choke (see page
Category
Specifications
PSD1-M_P020 with line
choke
230 V
400 V
480 V
Mains voltage
230 VAC ±10 % 50-60 Hz
400 VAC ±10 % 50-60 Hz
480VAC ±10% 50-60Hz
Rated voltage
3 AC 230 V
3 AC 400 V
3 AC 480 V
Input Current [rms]
44 A
44 A
40 A
Output voltage
325 VDC ±10 %
565 VDC ±10 %
680 VDC ±10 %
Output power
15.5 kW
27 kW
30 kW
Pulse power (<5 s)
31 kW
54 kW
60 kW
Power dissipation
140 W
140 W
140 W
Maximum fuse rating per
device
2 special purpose fuses in
line are required
Cable protection measure:
MCB (K characteristic) with a rating of 50A / 4xxVAC (depending on the input voltage)
Recommendation: (ABB) S203U-K50 (440VAC)
Device protection measure:
Circuit breakers 80A / 700VAC per supply leg in accordance with UL category JFHR2
Requirement: Bussmann 170M1366 or 170M1566D
Earth leakage current
Current on the mains PE (see page 24) (>3,5 mA)
Supply networks
Possible supply networks (see page 24): TN
The specified performance data are only valid in connection with
line choke
(see
page 87) IND-0002-01 or IND-0002-02 (UL).