
Installation of the multi-axis system PSD1-M
62 (109)
192-011006N8 2019-07
09.10.19 09:27
5.12.6.
X9: Control voltage 24 VDC mains module
Connector X9
Pin Designation
Line cross sections:
minimum: 0.5mm
2
with conductor sleeve
maximum: 6mm
2
with conductor sleeve
(AWG: 20 ... 10)
1
+24V
2
GND24V
Device type
PSD1-M_P
Voltage operating range
21 - 27VDC
Ripple
0,5Vpp
Requirement according
to safe extra low
voltage (PELV)
yes (class 2 mains module)
Electric current drain
PSD1-M_P010: 0.2A
PSD1-M_P020: 0.3 A
5.12.7.
X41 Mains supply (mains module PSD1-M_P)
Device protection
By cyclically switching on and off the power voltage, the input current limitation
can be overloaded, which may cause damage to the device.
Wait at least one minute between two switching on processes!
5.12.7.1
X41 Mains supply PSD1-M_P connector assignment
Pin Designation
PE
Earth conductor
L3
Phase 3
L2
Phase 2
L1
Phase 1
Only three-phase operation of the PSD1-M_P devices is permitted!
Please observe the notes in chapter “
Operating conditions for CE-conform
operation
(see page 13)“.
Caution - Risk of electric shock!
Always switch off devices before wiring them!
Dangerous voltages are still present until 10min. after switching off the power
supply.
Please check that no voltages are present (<50 V) at the output terminals DC+
and DC- (X63/3 & X63/5).