background image

K3.1.114o Manual NitroFlow Mobile 

 

- 27 - 

ATTENTION 
The response time of the measurement is slow. Change the flow in small steps of a quarter 
turn per step and wait until the display reading changes. 

Do not close the flow control valve fully. 

Adjusting the purity must preferably be done when the system is at normal operating 
temperature after it has run for some time (1-2 hrs) 

Adjusting the purity must be done while all sheet metal is mounted on the appliance 

5.  Once the desired purity has been reached, fasten the lock not on the spindle of the purity control valve 

securely. Make sure you do not change the setting. 

ATTENTION 
Fastening the lock nut too tightly can have an influence on the purity of the output 

7.4 

Control of the outlet pressure 

The outlet pressure of the generator can be controlled in two ways depending on whether is stored in a vessel or 
not.

No nitrogen vessel installed:

 Excess nitrogen will be vented; generator will run continuously. The 

-function

must be off. 

x

 

Close the ball valve V2 (refer to §3.3) at the outlet while the system is running. 

x

 

Adjust the back pressure valve PCV (refer to §3.3) such that the outlet pressure on the default main 
screen reads 8.0 bar(g)/116 psig at maximum. The lower the pressure is set the better for energy 
consumption reasons and compressor life. 

x

 

Open the ball valve V2 at the outlet. 

Nitrogen vessel installed: 

Excess nitrogen will be stored; generator will start and stop automatically. To set the 

pressure switch (PSH) function in the software for this situation, proceed as follows: 

x

 

Make sure the ball valve at the outlet (refer to §3.3) is open. 

x

 

Close PCV completely (turn right) (refer to §3.3). 

x

 

Set the switch-on pressure at maximum 7.0 bar(g). Switch-off pressure 8.0 bar(g). The lower the 
pressure is set the better for the energy consumption reasons and compressor life. 

x

 

Set the difference between the switch on and off pressure preferably not less than 1 bar. Smaller 
differences will result in frequent switching which will shorten the life of the compressors. 

NOTE 
After the unit switches off due to reaching switch off pressure in the storage tank, the unit 
cannot switch on within 5 minutes after the switch-off. The switch-on delay is there to prevent 
too frequent start-up of the compressors that shorten the compressor life. 

7.5 Stop 

generator 

1.  Press the ON/OFF button to switch the unit OFF (in case it is operating). 

2.  Switch off the power switch before you perform maintenance. 

3.  Make sure the system is depressurised; check the internal pressure level in the maintenance menu 

(screen 3/5) 

4.  When you restart afterwards there is a 3 minutes delay before it starts again. 

Содержание NitroFlow Basic Series

Страница 1: ...Nitrogen Gas Generator NitroFlow Basic Original Language User Guide aerospace climate control electromechanical filtration fluid gas handling hydraulics pneumatics process control sealing shielding EN...

Страница 2: ...otifying the customer The contents of this manual can also be changed without prior warning This manual is valid for the generator in its standard version Parker can therefore not be held liable for s...

Страница 3: ...TECHNICAL SPECIFICATIONS 12 4 1 General 12 4 2 Capacity data 14 4 3 Maintenance parts 14 5 INSTALLATION 15 5 1 Transport 15 5 2 Define location 15 5 3 Unpack and check equipment 15 5 4 Connect nitroge...

Страница 4: ...Flow Mobile 3 8 TROUBLESHOOTING 28 8 1 Error list 28 8 2 Alarm messages 28 9 MAINTENANCE 30 9 1 Maintenance schedule 30 9 2 Calibrate oxygen sensor 30 9 3 Cleaning 30 10 ELECTRICAL SCHEME 31 11 DECLAR...

Страница 5: ...nce to this rule as well as any consequential damage loss and costs are the responsibility of the owner and the user Information All information in this manual including additional drawings and techni...

Страница 6: ...or improper use The generator is in compliance with the prevailing directives and standards Only use this generator in a technically perfect condition in conformity with the purpose as described above...

Страница 7: ...generator generates nitrogen as a product Oxygen enriched air is released as waste Warning x Nitrogen can cause suffocation x Oxygen enriched air leads to increased risk of fire in the event of contac...

Страница 8: ...yclable Optimal sizing of buffer tanks and setting of the pressure switch will result in minimal energy consumption The lower the delivery pressure the longer the lifetime of the system According to E...

Страница 9: ...0 9 argon 1 carbon dioxide water vapor and traces of other inert gasses Pressurised air A is led through hollow fibre membranes B The various air components diffuse through the porous wall of the memb...

Страница 10: ...e Control Valve PCV 8 Nitrogen Outlet 4 Purity Adjustment Valve FCV 9 Ventilation Outlet Keep Clear 5 Touch Screen Display 3 4 Process diagram The generator can be connected directly to the nitrogen c...

Страница 11: ...et carbon adsorber LP Air compressor RKV Start up valve M Gas separation membrane PI1 Membrane pressure indicator FCV Flow control valve HP Nitrogen compressor PCV Nitrogen pressure relief valve PSH P...

Страница 12: ...en outlet C Inlet carbon adsorber LP Air compressor RKV Start up valve M Gas separation membrane PI1 Membrane pressure indicator FCV Flow control valve PCV Nitrogen pressure relief valve PSH Pressure...

Страница 13: ...ory II Altitude 2000 m 6562 ft Air quality Normal clean ambient air relative humidity 90 Max ambient relative humidity 80 to 31 C 50 at 40 C Noise level 58 dB A 1 meter 3 ft Dimensions and connections...

Страница 14: ...Delay 30 Alarm settings O2 low Active No Stop 0 Level 0 0 Delay 30 Alarm settings Pin high Active No Stop 0 Level 13 Delay 30 Alarm settings Pin low Active No Stop 0 Level 2 Delay 30 Alarm settings P...

Страница 15: ...30 32 38 Capacity at nominal conditions x Ambient temperature 20 C 68 F x Ambient pressure 1013 mbar a LP Low Pressure max 2 bar g 29 psig nitrogen pressure HP High Pressure max 8 bar g 116 psig nitro...

Страница 16: ...nts x Minimum clearance of 50 cm on all sides back left right and top as to facilitate heat removal x Indoors x Dry x No continuous direct irradiation by sunlight x Away from heat sources x Properly v...

Страница 17: ...nt 10 mA Voltage internal power supply UA1 Oxygen concentration Analogue output Input impedance to reach 0 mA 20 mA 200 Ohm UA2 Outlet pressure K5 Start stop signal to external booster Volt Free Relay...

Страница 18: ...ult When flashing there is an alarm touch the symbol and the current alarm will be shown Status of unit A Can be OFF RUN STAND BY ALARM P RELIEF Menu button touch to go to settings menu Switch ON OFF...

Страница 19: ...ch settings menu button in the main screen refer to 6 2 Function Access to different menus Symbol Menu Access to log on menu refer to 6 3 1 Access to alarm settings menu refer to 6 3 2 Access to press...

Страница 20: ...de is back to default value 1234 6 3 2 Alarm settings menu Access Touch alarm settings menu button in settings screen see 6 3 2 Function Set different alarms In the alarm settings menu it is possible...

Страница 21: ...s exceeded Level 0 16 O2 100 84 N2 For screen 1 6 and 2 6 this is the oxygen or nitrogen level at which the alarm is set Level 0 13 BAR 0 188 5 PSI For screen 3 6 and 4 6 This is the pressure level at...

Страница 22: ...ill switch on and off can be set To change the settings touch the button in front of the text Button Selection Result P switch Yes Pressure switch is active P switch No Pressure switch is not active U...

Страница 23: ...nnecting the printed circuit board to an external device Remote No Unit cannot be controlled from a remote location Pincode Yes Settings are instantly protected with a pin code Return to log on menu a...

Страница 24: ...to display temperature in F 6 3 6 Maintenance menu Access Touch maintenance menu button in settings screen refer to 6 3 Function Shows maintenance status and offers calibration possibility The mainten...

Страница 25: ...anation O2 20 9 Calibrate O2 sensor to 20 9 Contact Parker s technical support team Flow Factor Only visible when selected Show Flow in the options menu refer to 6 3 4 and when the unit is running Cal...

Страница 26: ...a Alarms as well as status of the sensors are saved on the SD card The time between the logging saving of this data to the memory card can be chosen in the data logging menu Button Selection Result In...

Страница 27: ...hed off in case of no nitrogen demand 8 The purity of the generator is factory set as required To adjust the oxygen content adjust the purity control valve FCV Refer to 7 3 for instructions 9 The pres...

Страница 28: ...er the pressure is set the better for energy consumption reasons and compressor life x Open the ball valve V2 at the outlet Nitrogen vessel installed Excess nitrogen will be stored generator will star...

Страница 29: ...er for service Residual oxygen content too high Pressure in nitrogen storage vessel over 8 bar g because of erroneous setting of pressure switch Reset pressure switch levels Ambient temperature lower...

Страница 30: ...rature sensor fails T Inlet sensor fail On Status of temperature of compressor box 1 Temp comp1 On Status of temperature of compressor box 2 Temp comp2 On Oxygen sensor needs to be calibrated Calibrat...

Страница 31: ...air 2 Wait for 60 seconds 3 Then enter again the maintenance menu screen 3 5 wait until the oxygen level is stable 4 Then go to screen 5 5 and touch O2 20 9 button The system will ask for confirmatio...

Страница 32: ...K3 1 114o Manual NitroFlow Mobile 31 10 Electrical scheme...

Страница 33: ...K3 1 114o Manual NitroFlow Mobile 32 11 Declaration of Conformity...

Страница 34: ...NOTES...

Страница 35: ......

Страница 36: ...arker com NL The Netherlands Oldenzaal Tel 31 0 541 585 000 parker nl parker com NO Norway Asker Tel 47 66 75 34 00 parker norway parker com PL Poland Warsaw Tel 48 0 22 573 24 00 parker poland parker...

Отзывы: