K3.1.114o Manual NitroFlow Mobile
- 20 -
Button Selection
Result
Active
No
Alarm function for this parameter is not active
Active
Yes
Alarm function for this parameter is active; alarm messages must
be reset manually
Active
Auto reset
Alarm function for this parameter is active; When alarm level is
not exceeded any longer before manual reset, the alarm will reset
itself
Stop
Yes
Generator will switch off in case alarm level is exceeded
Stop
No
An alarm signal will be given but generator will continue to run in
case alarm level is exceeded
Level
0-16% O
2
100 – 84% N
2
For screen 1/6 and 2/6: this is the oxygen- or nitrogen level* at
which the alarm is set.
Level
0-13 BAR*
0-188.5 PSI*
For screen 3/6 and 4/6.
This is the pressure level at which the alarm is set
Level
0-10 BAR*
0-145 PSI*
For screen 5/6 and 6/6.
This is the pressure level at which the alarm will appear.
Delay
0-300 sec
Delay time in seconds between the moment that the alarm level
has been exceeded and signaling; this feature prevents false
alarms in case of short spikes
*see also local settings
-menu
ATTENTION:
It is impossible to set O
2
low at a higher level than O
2
high. The setting of O
2
low is limited once
O
2
high has been set. Therefore, first set O
2
high level before setting the O
2
low level.