14
Gemini GT6 Hardware Installation Guide
Step 2 – Connecting AC Power
GT6-L5 and GT6-L8 can be operated only at 120VAC.
GT6-U5 and GT6-U8 can be operated at 120VAC or single phase 240VAC.
Acceptable ranges of AC input voltage are listed below:
Drive
AC Input Range
GT6-L5
95VAC – 132VAC
GT6-L8
95VAC – 132VAC
GT6-U5
95VAC – 132VAC and 190VAC – 264VAC
GT6-U8
95VAC – 132VAC and 190VAC – 264VAC
CAUTION
You must connect V DBL to L2/N on GT6-U5 and GT6-U8 to enable the voltage
doubler for 120VAC operation.
WARNING
You must connect the drive’s protective conductor terminal, marked with the
symbol, to a reliable system safety earth. Make the connection directly, by means
of a low impedance path less than or equal to 0.1 ohm (no fuses, etc.). Under
normal operation, no current should flow through the safety earth connection.
WARNING
The drive’s barrier strip terminals are at hazardous voltages when power is applied
to the drive, and up to 30 seconds after power is removed. Reinstall the clear
plastic terminal cover after you make connections.
Fuse Information
Gemini drives have no internal fuses. For safety, you must provide a fuse in each
of the AC input lines. Recommended fuse types and sizes are:
GT6-L5/GT6-L8 (120VAC)
GT6-U5/GT6-U8 (120VAC)
GT6-U5/GT6-U8 (240VAC)
125VAC Time Delay
125VAC Time Delay
125VAC Time Delay
10 amp
10 amp
10 amp
Type RK5 or better
Type RK5 or better
Type RK5 or better
The next table lists part numbers for suitable fuses, from several manufacturers:
Amps:
Bussman:
Gould:
Littelfuse:
Grainger:
10
FRNR10
TR10R
FLNR10
1A693
GT6-L5 and GT6-L8 AC Power Connections
Connections are illustrated in the next drawing, on the left.
CAUTION
Do not operate GT6-L5/8 above 132VAC, or the drive will be
permanently damaged.