2: Calibrating the Control Board
NO POWER IS CONNECTED AT THIS STAGE
2.1
Lift the hinged terminal cover to reveal
the control board.
Enter the settings for Armature
Current, Field Current and Armature
Voltage.
X100
X10
X1
X10
X1
X0.1
SW1 SW2 SW3 SW4 SW5 SW6
IA CAL
IF CAL
ON
1
2
3
4
VA CAL
SW7
Armature
Current
(IA CAL)
Note the maximum armature current from the motor rating plate and set this value using SW1, SW2 and SW3.
The switches set Amps in hundreds, tens and units. The illustration shows an IA CAL setting of 77A.
Field
Current
(IF CAL)
Note the nominal field current from the motor rating plate and set this value using SW4, SW5 and SW6. The
switches set Amps in tens, units and tenths. The illustration shows an IF CAL setting of 5.7A. The maximum
current is 19.9A, setting a higher value than this results in 0A.
Armature
Voltage
(VA CAL)
Set this using the 4-way
switch, SW7. The switch
sets voltage according to
the table. The illustration
shows a VA CAL setting of
200V.
(A “1” indicates that
the switch is ON).
VA
Armature Volts VA (Volts)
Switch 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525
1 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
2 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0
3 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0
4 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0
2.2
CONNECT THE AUXILIARY SUPPLY:
Remove 3-phase fuses (
6
). Re-instate branch circuit protection or circuit
breaker (
8
). Check that the auxiliary voltage is correct. The MMI will now display the Welcome screen.
AUXILIARY POWER ONLY IS CONNECTED AT THIS STAGE
Use a digital voltmeter to check for +24V rail at terminal C9, +10V rail at terminal B3, -10V rail
at terminal B4. The drive will be using the default speed feedback option ARM VOLTS FBK.
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
SPEED FBK SELECT