3: Initial Start-Up Routine
AUXILIARY POWER ONLY IS CONNECTED AT THIS STAGE
Complete steps 3.1 to 3.12
3.1
Write down the MAIN CURR.
LIMIT parameter’s value
here:
.......................................
Set to 0.00%
3.2
Check that ANIN 5 (A6) is
+10V. If not, check the
wiring link between terminals
A6 and B3.
3.3
Save your settings. Press the
Ï
(UP) key, as instructed.
3.4
With the Program Stop and Coast Stop LEDs illuminated:
Apply the "Start/Run" command to C3.
The main 3-phase contactor should close and remain energised.
Quickly remove the "Start/Run" command from C3.
The main 3-phase contactor should open and remain de-energised.
IMPORTANT
The main contactor should never
be operated by any means other
than the drive's internal controls,
nor should any additional
circuitry be placed around the
contactor coil circuit.
Didn't work?
Remove the auxiliary power and check start/stop sequencing and contactor wiring.
3-Phase Alarm?
The drive has tripped because there is no 3-phase supply connected. To clear the alarm press
the
E
key. Repeat the test at
3.4
again, but quickly remove the "Start/Run" command before the alarm has time to
initiate.
WARNING
Do not continue until the stop/start circuits and contactor operate correctly.