Warranty conditions 

192-

120102N23 2016-04

 

Before you can work on the device, the supply voltage must be switched off at the
L1, L2 and L3 clamps. Wait at least 15 minutes so that the power direct current
may sink to a secure value (<50V). Check with the aid of a voltmeter, if the
voltage at the DC+ and DC- clamps has fallen to a value below 50V.
Danger of electric shock in case of non respect.

 

Do never perform resistance tests with elevated voltages (over 690V) on the
wiring without separating the circuit to be tested from the drive.

 

Please exchange devices only in currentless state and, in an axis system, only in
a defined original state.

 

If the axis controller is replaced, it is absolutely necessary to transfer the
configuration determining the correct operation of the drive to the device, before
the device is put into operation. Depending on the operation mode, a machine
zero run will be necessary.

 

The device contains electrostatically sensitive components. Please heed the
electrostatic protection measures while working at/with the device as well as
during installation and maintenance.

2.6 

Warranty conditions 

 

 

The device must not be opened.

 

Do not make any modifications to the device, except for those described in the
manual.

 

Make connections to the inputs, outputs and interfaces only in the manner
described in the manual.

 

Fix the devices according to the 

mounting instructions.

 (see on page 15)

We cannot provide any guarantee for other mounting methods.

Note on exchange of options 

Device options must be exchanged in the factory to ensure hardware and software 
compatibility.   

 

When installing the device, make sure the heat dissipators of the device receive
sufficient air and respect the recommended mounting distances of the devices
with integrated ventilator fans in order to ensure free circulation of the cooling air.

 

Make sure that the mounting plate is not exposed to external temperature
influences.

2.7 

Conditions of utilization 

 

2.7.1. 

Conditions of utilization for CE-conform operation 

- Industry and trade -

The  EC  guidelines  for  electromagnetic  compatibility 

2014/30/EU

  and  for  electrical

 

operating devices for utilization within certain voltage limits 

2014/35/EU

 are fulfilled

 

when the following boundary conditions are observed:

Operation of devices only in the state in which they are delivered. 

 

In order to ensure contact protection, all mating plugs must be present on the 
device connections even if they are not wired. 
Please respect the specifications of the manual resp. of the help function, 
especially the technical characteristics (mains connection, circuit breakers, output 
data, ambient conditions,...). 

 

2.7.1.1 

Conditions of utilization mains filter 

Mains filter:

 A mains filter is required in the mains input line if the motor cable exceeds a 

certain length. Filtering can be provided centrally at the system mains input or 
separately for each device. 

 

Use of the devices in a commercial and residential area (limit value class in 
accordance with EN 61800-3) 

The following mains filters are available for independent utilization: 

 

Содержание Compax3S

Страница 1: ...ve the right to make technical changes 20 04 16 14 42 192 120102N23 2016 04 The data correspond to the current status at the time of printing Compax3S quick reference guide Single axis devices 192 121...

Страница 2: ...ications German Master created Parker Hannifin Manufacturing Germany GmbH Co KG Electromechanical Drives Division EME Robert Bosch Strasse 22 77656 Offenburg Germany Tel 49 0781 509 0 Fax 49 0781 509...

Страница 3: ...nal HTLM help please refer to our website 1 1 C3 ServoManager PC requirements Minimum requirements Operating system MS Windows XP SP3 MS Vista 32 Bit Windows 7 32 Bit 64 Bit Browser MS Internet Explor...

Страница 4: ...utilization 9 2 7 1 Conditions of utilization for CE conform operation 9 2 7 2 Conditions of utilization for UL certification Compax3S 11 2 7 3 Current on the mains PE leakage current 12 2 7 4 Supply...

Страница 5: ...pax3S025V2 supplement Compax3S063V2 supplement Compax3S100V2 supplement Compax3S150V2 supplement Compax3S015V4 supplement Compax3S038V4 supplement Compax3S075V4 supplement Compax3S150V4 supplement Com...

Страница 6: ...supply data Power Output Output data 5 Designation of the feedback system F10 Resolver F11 SinCos Single or Multiturn F12 Feedback module for direct drives 6 Device interface I10 Analog step directio...

Страница 7: ...h the respectively valid environmental laws The following table states the materials suitable for recycling and the materials which have to be disposed of separately Material suitable for recycling Di...

Страница 8: ...echniques and the local emergency rescue services who have read and will observe the safety instructions who have read and observe the manual or help or the sections pertinent to the work to be carrie...

Страница 9: ...de any guarantee for other mounting methods Note on exchange of options Device options must be exchanged in the factory to ensure hardware and software compatibility When installing the device make su...

Страница 10: ...n the motor type 100 m Corresponding to the specifications of the terminal clamp with a temperature range of up to 60 C Cable installation Signal lines and power lines should be installed as far apart...

Страница 11: ...Temperature 45 C Motor over temperature monitoring is only supported if the external temperature sensor is connected Suitable for use on a circuit capable of delivering at least 5000 symmetrical amper...

Страница 12: ...leakage current depends on the following factors Length and properties of the motor cable Switching frequency Operation with or without external mains filter Motor cable with or without shield network...

Страница 13: ...Parker EME EC declaration of conformity 192 120102N23 2016 04 13 2 8 EC declaration of conformity...

Страница 14: ...ax3 axis controller Device status LEDs Right LED red Left LED green Voltages missing off off During the booting sequence alternately flashing No configuration present SinCos feedback not detected Comp...

Страница 15: ...ting and dimensions Compax3S100V2 and S0xxV4 16 Mounting and dimensions Compax3S150V2 and S150V4 17 Mounting and dimensions Compax3S300V4 18 3 3 1 Mounting and dimensions Compax3S0xxV2 Mounting 3 sock...

Страница 16: ...20102N23 2016 04 3 3 2 Mounting and dimensions Compax3S100V2 and S0xxV4 Mounting 3 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convectio...

Страница 17: ...2016 04 17 3 3 3 Mounting and dimensions Compax3S150V2 and S150V4 Mounting 4 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convection At t...

Страница 18: ...d dimensions Compax3S300V4 Mounting 4 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convection At the side 15mm At the top and below at le...

Страница 19: ...ller type S015V4 S038V4 S075V4 S150V4 S300V4 Continuous working voltage Three phase 3 400VAC 480VAC 80 528VAC 50 60Hz Receiver current consumption 3Aeff 6Arms 10Arms 16Arms 22Arms Maximum fuse rating...

Страница 20: ...Technical Data Single axis devices 20 192 120102N23 2016 04...

Отзывы: