Introduction

 

Single axis devices

 

12 

192-

120102N23 2016-04

2.7.3. 

Current on the mains PE (leakage current) 

 

 

This product can cause a direct current in the protective lead. If a residual current 
device (RCD) is used for protection in the event of direct or indirect contact, only 
a type B (all current sensitive) RCD is permitted on the current supply side of this 
product . Otherwise, a different protective measure must be taken, such as 
separation from the environment by doubled or enforced insulation or separation 
from the mains power supply by means of a transformer. Respect the supplier's 
instructions. 

Mains filters do have high leakage currents due to their internal capacity. An 
internal mains filter is usually integrated into the servo controllers. Additional 
discharge currents are caused by the capacities of the motor cable and the motor 
winding. Due to the high clock frequency of the power output stage, the leakage 
currents do have high-frequency components. Please check if the FI protection 
switch is suitable for the individual application. 
If an external mains filter is used, an additional leakage current will be produced. 
The figure of the leakage current depends on the following factors: 

 

Length and properties of the motor cable

 

Switching frequency

 

Operation with or without external mains filter

 

Motor cable with or without shield network

 

Motor housing grounding (how and where)

Remark: 

 

The leakage current is important with respect to the handling and usage safety of
the device.

 

A pulsing leakage current occurs if the supply voltage is switched on.

Please note: 

The device must be operated with effective grounding connection, which must 
comply with the local regulations for high leakage currents (>3.5 mA). 
Due to the high leakage currents it is not advisable to operate the servo drive with 
an earth leakage circuit breaker. 

 

2.7.4. 

Supply networks 

This product is designed for fixed connection to TN networks (TN-C, TN-C-S or 
TN-S). Please note that the line-earth voltage may not exceed 300VAC.   

 

When grounding the neutral conductor, mains
voltages of up to 480VAC are permitted.

 

When grounding an external conductor (delta
mains, two-phase mains), mains voltages (external
conductor voltages) of up to 240VAC are
permitted.

Devices which are to be connected to an IT network must be provided with a 
separating transformer. Then the devices are operated locally as in a TN network. 
The secondary sided center of the separating transformer must be grounded and 
connected to the PE connector of the device. 

 

Содержание Compax3S

Страница 1: ...ve the right to make technical changes 20 04 16 14 42 192 120102N23 2016 04 The data correspond to the current status at the time of printing Compax3S quick reference guide Single axis devices 192 121...

Страница 2: ...ications German Master created Parker Hannifin Manufacturing Germany GmbH Co KG Electromechanical Drives Division EME Robert Bosch Strasse 22 77656 Offenburg Germany Tel 49 0781 509 0 Fax 49 0781 509...

Страница 3: ...nal HTLM help please refer to our website 1 1 C3 ServoManager PC requirements Minimum requirements Operating system MS Windows XP SP3 MS Vista 32 Bit Windows 7 32 Bit 64 Bit Browser MS Internet Explor...

Страница 4: ...utilization 9 2 7 1 Conditions of utilization for CE conform operation 9 2 7 2 Conditions of utilization for UL certification Compax3S 11 2 7 3 Current on the mains PE leakage current 12 2 7 4 Supply...

Страница 5: ...pax3S025V2 supplement Compax3S063V2 supplement Compax3S100V2 supplement Compax3S150V2 supplement Compax3S015V4 supplement Compax3S038V4 supplement Compax3S075V4 supplement Compax3S150V4 supplement Com...

Страница 6: ...supply data Power Output Output data 5 Designation of the feedback system F10 Resolver F11 SinCos Single or Multiturn F12 Feedback module for direct drives 6 Device interface I10 Analog step directio...

Страница 7: ...h the respectively valid environmental laws The following table states the materials suitable for recycling and the materials which have to be disposed of separately Material suitable for recycling Di...

Страница 8: ...echniques and the local emergency rescue services who have read and will observe the safety instructions who have read and observe the manual or help or the sections pertinent to the work to be carrie...

Страница 9: ...de any guarantee for other mounting methods Note on exchange of options Device options must be exchanged in the factory to ensure hardware and software compatibility When installing the device make su...

Страница 10: ...n the motor type 100 m Corresponding to the specifications of the terminal clamp with a temperature range of up to 60 C Cable installation Signal lines and power lines should be installed as far apart...

Страница 11: ...Temperature 45 C Motor over temperature monitoring is only supported if the external temperature sensor is connected Suitable for use on a circuit capable of delivering at least 5000 symmetrical amper...

Страница 12: ...leakage current depends on the following factors Length and properties of the motor cable Switching frequency Operation with or without external mains filter Motor cable with or without shield network...

Страница 13: ...Parker EME EC declaration of conformity 192 120102N23 2016 04 13 2 8 EC declaration of conformity...

Страница 14: ...ax3 axis controller Device status LEDs Right LED red Left LED green Voltages missing off off During the booting sequence alternately flashing No configuration present SinCos feedback not detected Comp...

Страница 15: ...ting and dimensions Compax3S100V2 and S0xxV4 16 Mounting and dimensions Compax3S150V2 and S150V4 17 Mounting and dimensions Compax3S300V4 18 3 3 1 Mounting and dimensions Compax3S0xxV2 Mounting 3 sock...

Страница 16: ...20102N23 2016 04 3 3 2 Mounting and dimensions Compax3S100V2 and S0xxV4 Mounting 3 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convectio...

Страница 17: ...2016 04 17 3 3 3 Mounting and dimensions Compax3S150V2 and S150V4 Mounting 4 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convection At t...

Страница 18: ...d dimensions Compax3S300V4 Mounting 4 socket head screws M5 Stated in mm Please respect an appropriate mounting gap in order to ensure sufficient convection At the side 15mm At the top and below at le...

Страница 19: ...ller type S015V4 S038V4 S075V4 S150V4 S300V4 Continuous working voltage Three phase 3 400VAC 480VAC 80 528VAC 50 60Hz Receiver current consumption 3Aeff 6Arms 10Arms 16Arms 22Arms Maximum fuse rating...

Страница 20: ...Technical Data Single axis devices 20 192 120102N23 2016 04...

Отзывы: