Compax3 device description
Function of the
LEDs on the front panel
20
192-120102 N7 - February 2004
Caution!
When the control voltage is missing there is no indication whether or
not high voltage supply is available.
3.2.1.
Function of the LEDs on the front panel
State
LED red
LED green
Voltages missing
off
off
While booting
alternately flashing
!
No configuration present.
!
SinCos feedback not detected.
!
IEC program not compatible with the
firmware.
!
For F12: Hall signals invalid.
flashing
off
Axis without current excitation
off
Flashes slowly
Power supplied to axis; commutation calibration
running
off
Flashes quickly
Axis with current excitation
off
on
Axis in fault status / fault present
on
off
3.2.2.
Power supply plug X1 for 230VAC devices
PIN
Description
1
L
2
N
3
PE
Mains connection: Compax3 S0xx V2
Controller type
S025 V2
S063 V2
Mains voltage
Single phase 10%
80-10% / 50-60Hz
Rated input current
6Aeff
16Aeff
Maximum fuse rating per device
10A (automatic circuit
breaker K)
16 A (automatic circuit
breaker K)
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after