b. Send the
THALL
command. It should report a number in the range
of 1–6, which indicates the phase wires are connected correctly. If
the response is
Ø
or
7
, a fault exists. Check the motor phase wiring
c. Send the
TPE
command and turn the motor shaft. Verify the
encoder is counting in the correct direction. Turning the shaft
clockwise results in positive encoder counts when
CMDDIR
is set
to zero (Ø). If not, check the encoder feedback wires and reset the
drive.
Hall Sensors
The troubleshooting procedures in this section assume that a terminal
emulator connection is established with the drive. The procedures assist you
in resolving a Hall fault (
ERROR
bit
E37-Bad Hall State
). Several problems
can cause a Hall fault; the following checklist will help identify these
problems.
Troubleshooting Checklist
1. Does
THALL
report either 0 or 7?
If yes, see Problem 1 or 2, below.
2. Does
THALL
change if you move the motor by hand?
If no, see Problem 2, below.
3. Does
THALL
have six distinct Hall states from 1 to 6? (No numerical
order is necessary.)
If no, see Problem 2, below.
4. Does
THALL
report the six distinct Hall states
n
times as the rotor turns
one revolution, where
n
is equal to the number of pole-pairs (
DPOLE
)?
(Linear motors:
n
= pitch)
If no, see Problem 2 or 3, below.
5. Does
THALL
report the Hall state sequence [1, 5, 4, 6, 2, 3, 1...] as the
motor turns clockwise? (Clockwise means
TPE
is increasing when
CMDIR
set to zero (Ø); it is also the direction the motor turns in
DMODE1
.)
If no, see Problem 4, below.
6. Does
ERROR
report a Hall fault each time the drive is enabled
(
DRIVE1
), even though the Hall state sequence is correct?
If yes, see Problem 4, below.
7. Does the Hall fault occur irregularly?
If yes, see Problem 6, below.
Possible Problems
1. No Hall states are seen by the drive.
2. The cable is not connected, or is connected incorrectly (incorrectly
wired).
3.
DPOLE
or
DMEPIT
is not set correctly.
4. Either the motor wires or the Hall wires are connected incorrectly.
Use Procedure 1 to fix this problem by changing the motor wires.
Use Procedure 2 to fix this problem by changing the Hall wires.
5. The Hall wires or the encoder wires may have loose connections,
causing intermittent faults.
Appendix H ETHERNET Powerlink 191
www.comoso.com
Содержание ACR9000
Страница 1: ...www comoso com ...
Страница 33: ...Parker Hannifin Figure 7 ACR9040 Front Panel Interfaces Chapter 2 Specifications 33 www comoso com ...
Страница 112: ...Appendix B VM25 Breakout Module A P P E N D I X B VM25 Breakout Module IN THIS CHAPTER Overview 113 www comoso com ...
Страница 114: ...Appendix C VM26 Breakout Module A P P E N D I X C VM26 Breakout Module IN THIS CHAPTER Overview 115 www comoso com ...
Страница 143: ...Appendix F Drive Talk A p p e n d i x F Drive Talk IN THIS CHAPTER Quick Startup 144 www comoso com ...
Страница 159: ...Parker Hannifin Figure 40 ACR9040 Panel Layout Dimensions Appendix G Regulatory Compliance 159 www comoso com ...
Страница 165: ...Parker Hannifin Figure 43 ACR9030 Front Panel Appendix H ETHERNET Powerlink 165 www comoso com ...