![Parker AC30 series Скачать руководство пользователя страница 219](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313219.webp)
Compliance
C-6
AC30 series Variable Speed Inverter
EMC COMPLIANCE (4KHZ)
Standard EN 61800-3
Frame D ≤ 2.2kW
Frame D > 2.2kW
Frame E
Frame F
C
on
du
ct
ed
E
mi
ss
ion
s
A
C
S
up
po
rte
d
In
ve
rte
rs
Category C1
When fitted with the specified
external filter & EMC filter kit, refer
to C16-17
Maximum cable length 5 m
When fitted with the specified
external filter & EMC filter kit,
refer to C16-17
Maximum cable length 5 m
Refer to C-9 for the use of a suitable
external filter with the required
characteristics
Refer to C-10 for the use of a
suitable external filter with the
required characteristics
Category C2
Product supplied as a component,
a suitable external filter is required
When fitted with an EMC filter kit
(internal filter, clamping bracket
and ferrite), refer to C-17
Maximum cable length 10 m
When fitted with an EMC filter kit
(internal filter, clamping bracket and
ferrite), refer to C-17
Maximum cable length 10 m
When fitted with an EMC filter kit
(internal filter, clamping bracket and
ferrite), refer to C-18
Maximum cable length 10 m
When fitted with the specified external
filter & EMC filter kit, refer to C17
Maximum cable length 25 m
When fitted with the specified
external filter & EMC filter kit, refer to
C18
Maximum cable length 25 m
Category C3
Where I<=100A
Product supplied as a component,
a suitable external filter is required
When fitted with an internal filter
Maximum cable length 50 m
When fitted with an internal filter
Maximum cable length 50 m
When fitted with an internal filter
Maximum cable length 25 m (50m
with EMC filter kit, Refer to C-18)
DC
S
up
pli
ed
S
ys
te
m
Category C3
When supplied by AC to DC full bridge and required line choke. Maximum cable length 50 m.
Ra
dia
te
d
Em
iss
ion
ns
When mounted inside a cubicle with the required attenuation between:
Category C1
35-100MHz at 15dB
35-100MHz at 5dB
30-150MHz at 20dB
Category C2
35-100MHz at 5dB
No specific enclosure required
30-150MHz at 10dB
Category C3
No specific enclosure required
No specific enclosure required
No specific enclosure required
C
ab
le
R
eq
uire
men
ts
Power Supply
Cable Type
Unscreened
Segregation
From all other wiring (clean)
Length Limit
Unlimited
Motor Cable
Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Screen to Earth
Both ends
Output Choke
300 meters maximum
External Filter
to Drive
Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Length Limit
0.3 meters
Screen to Earth
Both ends
Brake Resistor Cable Type
Screened/Armoured
Segregation
From all other wiring (noisy)
Length Limit
25 meters
Screen to Earth
Both ends
Signal/Control
Cable Type
Screened
Segregation
From all other wiring (sensitive)
Length Limit
25 meters
Screen to Earth
Drive end only
8, 12, 16kHz will require extra filtering.
Содержание AC30 series
Страница 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Страница 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Страница 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Страница 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Страница 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Страница 58: ...4 37 Installation AC30 series Variable Speed Inverter AFE Control Wiring Excludes 7004 04 00 Wiring...
Страница 149: ...Setup Wizard 9 24 AC30 series Variable Speed Inverter MONITOR THE DRIVE Figure 9 15 Monitor the Drive and fine tune...
Страница 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Страница 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Страница 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Страница 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Страница 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...