Configuration Setup:
TH1
Motor Thermistor ‘+’ connection
TH2
Motor Thermistor ‘-’ connection
DX1
Run Forward:
24V digital input
STOA
24V input connected i.e., STO
DISABLED
(drive operational)
STOB
24V input connected i.e., STO
DISABLED
(drive operational)
Minimum STO Implementation:
This example shows ‘STO Request’ contacts that are used to invoke STO on the drive. These contacts are
required to close prior to running the drive:
Configuration Setup:
TH1
Motor Thermistor ‘+’ connection
TH2
Motor Thermistor ‘-’ connection
DX1
Run Forward:
24V digital input
STOA
24V input connected via ‘
STO Request
’ contacts
STOB
24V input connected via ‘
STO Request
’ contacts
To run the drive:
1. Close the ‘STO Request’ contacts.
2. Close the ‘Run Forward’ contact.
To stop the drive:
1. Open the ‘Run Forward’ contact and wait for the motor to come to a standstill.
To invoke STO:
1. When the motor is at standstill, open the ‘STO Request’ contacts.
2. STO will now be ‘Active’ on the drive, for as long as required.
Note: Opening the ‘STO Request’ contacts when the motor is running will result in the motor
coasting to a stop.
STO Request
Содержание AC20 Series
Страница 148: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 148 154 DOC 0017 04 EN A 22 03 2023 Frame 3 Frame 4...
Страница 150: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 150 154 DOC 0017 04 EN A 22 03 2023 Frame 3...
Страница 151: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual DOC 0017 04 EN A 22 03 2023 151 154 Frame 4 Frame 5...
Страница 152: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 152 154 DOC 0017 04 EN A 22 03 2023 Frame 6 Frames 7 8...
Страница 153: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual DOC 0017 04 EN A 22 03 2023 153 154 Frame 9 Frame 10...
Страница 154: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 154 154 DOC 0017 04 EN A 22 03 2023...