DOC-0017-04-EN: AC20 Series - Hardware Installation Manual
DOC-0017-04-EN-A 22.03.2023
35 (154)
Y-Capacitors & VDR Earth Disconnects
The AC20 products are fitted with EMC filter capacitors connected between ‘live’ AC Line (and in some
instances DC Link) circuits to earth. These capacitors are referred to as Y-Capacitors.
In some system applications where RCD’s are in circuit, or where the drive is connected on an IT supply,
these Y-Capacitors may need to be disconnected from earth. Removable links are provided to enable users
to perform this task.
By default:
- AC Line Y-Caps are connected to earth (‘EMC’ connector ‘J1’, is fitted in position 1 - 3).
- DC Link Y-Caps are connected to earth (‘P -> PE’ connector ‘J2’ is fitted in position 1 - 3).
Most products are also fitted with input line voltage suppression devices connected between ‘live’ AC Line
circuits to earth. These suppression devices are referred to as VDRs.
In some system applications where the product is exposed to large, transient voltage events on the power
supply that it is connected to, it is recommended that the VDRs are connected to earth as a means of
protecting the drives input rectification stage. Removable links are provided to enable users to perform this
task.
By default:
- VDRs are
NOT
connected to earth (‘VAR’ connector ‘Y1’, is fitted in position 2 - 4).
A summary of links fitted to each product is shown below:
1ø, 230V Products:
Frame
Size
Product Code
Motor
Power
(kW)
J1 ‘EMC’ (AC
Line Y-Cap)
Link:
Y1 ‘VAR’ (VDR)
Link:
J2 ‘P -> PE’ (DC
Link Y-Cap)
Link:
2
20G-12-0070...
1.5
x
x
20G-12-0100...
2.2
x
x
3ø, 230V Products:
Frame
Size
Product Code
Motor
Power
(kW)
J1 ‘EMC’ (AC
Line Y-Cap)
Link:
Y1 ‘VAR’ (VDR)
Link:
J2 ‘P -> PE’ (DC
Link Y-Cap)
Link:
2
20G-32-0070...
1.5
x
20G-32-0100...
2.2
x
3
20G-33-0170...
4.0
x
4
20G-34-0210...
5.5
x
x
5
20G-35-0300...
7.5
x
x
20G-35-0400...
11
x
x
Содержание AC20 Series
Страница 148: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 148 154 DOC 0017 04 EN A 22 03 2023 Frame 3 Frame 4...
Страница 150: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 150 154 DOC 0017 04 EN A 22 03 2023 Frame 3...
Страница 151: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual DOC 0017 04 EN A 22 03 2023 151 154 Frame 4 Frame 5...
Страница 152: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 152 154 DOC 0017 04 EN A 22 03 2023 Frame 6 Frames 7 8...
Страница 153: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual DOC 0017 04 EN A 22 03 2023 153 154 Frame 9 Frame 10...
Страница 154: ...DOC 0017 04 EN AC20 Series Hardware Installation Manual 154 154 DOC 0017 04 EN A 22 03 2023...