6
8903/RS RS485 Communications Interface
Preferred Cable Connection
Connection using the preferred cable (see Figure 7):
Connect one twisted pair to the signal terminals
A
and
B
.
Connect the power core, or another twisted pair, to the
Ground
terminal. It is
recommended to connect the Ground signal to earth
at one point only
on the RS485 bus.
The screen should be connected to the
Screen
terminal, and earthed
at one end of the cable
only
(the Earthing Screw may be used for this)
.
Figure 7. Preferred RS485 Wiring Configuration
Alternative Cable Connection
Connection using the alternative cable (see Figure 8):
Connect one twisted pair to the signal terminals
A
and
B
.
The screen should connected to the
Ground
terminal, and earthed
at one end of the cable
only
(the Earthing Screw may be used for this)
.
Figure 8. Alternative RS485 Wiring Configuration
*
* If the 8903/RS is the last node then the on-board terminator (T) may be used instead
screen
120O
B
A
Ground
Node 1
Screen
T
Node 2
Earthing
screw
screen
B
A
Node
n
T
B
A
T
screen
screen
10nF
10nF
120O
Screen
Screen
Ground
Ground