30
8903/RS RS485 Communications Interface
15 Write Multiple Coils
Not supported.
Request PDU:
Function code
1 byte
0x0F
Starting address
2 bytes
0x0000 to 0xFFFF
Quantity of outputs
2 bytes
N
Byte count
1 byte
N/8
Output value
N/8 bytes
value
Error Response:
Function code
1 byte
0x8F
Exception code
1 byte
01
16 Write Multiple Registers
This function is used to write a block of contiguous registers. The function allows a request
from a broadcast, in which case there is no response.
Request PDU:
Function code
1 byte
0x10
Starting address
2 bytes
0x0000 to 0xFFFF
Quantity of registers
2 bytes
1 to 123 (N)
Byte count
1 byte
2*N
Register value
N*2 bytes value
Response:
Function code
1 byte
0x10
Starting address
2 bytes
0x0000 to 0xFFFF
Quantity of registers 2 bytes
1 to 123 (N)
Error Response:
Function code
1 byte
0x90
Exception code
1 byte
02 or 03