31
8903/RS RS485 Communications Interface
Appendix C: Troubleshooting
LEDs
The LEDs status indicating possible errors are given in the table below. For more details see
section
Status and Activity LED Indications
.
Status LED
Activity LED
Description
Orange Orange -
Initialising – will change after a few moments
-
Incorrect 890 drive firmware - if the LEDs remain in
this state
Red / Green
50% flash
Off -
Configuring
-
Failure to configure - if the LEDs remain in this state
(see below)
DSE Configuration Error
If the RS485 is not configured correctly then the module list in DSE, or the Scratch Pad in
DSELite, will report a status of
LERROR
. The Status LED will flash 50% RED/GREEN (see
above). Possible configuration problems are:
•
An 8903/RS option is fitted without an RS485 fieldbus block in the DSE configuration. No
LERROR will be reported, but the Status LED will flash 50% RED/GREEN.
•
DSE configuration includes an RS485 fieldbus block without an 8903/RS option fitted to the
drive.
•
The RS485 fieldbus node address has not been configured (has a node address of 0).
•
The RS485 fieldbus block has a DSE register allocated without an input or output connector
associated with it. Unwanted DSE registers should be deleted.
•
The RS485 fieldbus block has a DSE register allocated with an input and an output fieldbus
connector of different DSE data types. If a DSE register is associated with both input and
output connectors both must be of the same type, i.e. VALUE, INTEGER or BOOLEAN.
MMI Error Diagnostics
The MMI diagnostics for the Modbus RTU function block can be found under the menu
SETUP::COMMUNICATIONS::MODBUS RTU. The diagnostics are described in the section
MMI Diagnostics
.
The possible reasons for error counters incrementing are given in the table below.
Error Counter
Reason
EXCEPTION
COUNT
-
An error response has been transmitted by the 8903/RS option
(see section
Modbus RTU:Exceptions)
.
-
The 8903/RS has received a frame with an unrecognised
Modbus function code.
CRC ERROR
COUNT
-
The 8903/RS has received a frame with an incorrect CRC
checksum. This could be due to noise corrupting the data.
CHAR ERR COUNT
The 8903/RS has received a character with either a framing error
or parity error.
-
Check all nodes have the same baud rate.
-
Check all nodes have the same parity.
-
Noise could be corrupting the data.
DATA EXD COUNT
The maximum data permitted in a Modbus request/response has
been exceeded.
-
Maximum number of Modbus read registers is 125.
-
Maximum number of Modbus write registers is 123.
RX ABORT COUNT
Excessive delay between characters has been detected whilst the
8903/RS option was receiving a frame (see section
Modbus
RTU: Inter-Frame Delay and Inter-Character Delay
). In this
case the received frame is ignored.