4
4. Doubling method
Z3
Z1
Z2
Z4
728: [1/2] [3/4] [5/6] [7/8]
Zone 1,3,5 & 7 use 1K resistor, zone 2,4,6 & 8 use 2.2K resistor.
Keypad 1 as zone 9 and keypad 2 as zone10, need to put 1K resistor for keypad zones.
[key in 090][ON key 8][ENTER], to enable zone doubling
[key in 088], [ON key MEM][ENTER], disable EOL.
AND program zone type in Step 1.
Important note: Once the panel is in zone doubling, ALL zones are Normally Closed (NC).
Note
: For zone doubling, the zone speed setting in address [053] should be [004] and above to avoid false
alarm caused by vibration sensors.
For Fire zone connections using 4-wire smoke detector
Once zone 3 is enable as FIRE zone in this zone doubling method:
[key in 090][ON key 1][ENTER], to disable zone 4.
[key in 100][ON key 3][ENTER], to program zone 3 as fire zone.
[key in 039], press [5][0], PGM to reset smoke detector
[key in 040], press [5][0], PGM to reset smoke detector
[key in 042], press [2ND][6], PGM to reset smoke detector
[key in 056], press [0][0][4], PGM to reset smoke detector
Note: Once zone 3 is a FIRE zone, zone 4 can not be used. Now, this zone 3 is a parallel wiring..
1 K
2.2
K
1K
2.2
K
1
C
2
3
C