![Paradox Hellas S.A. DEVELOPED Neon 2 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/paradox-hellas-s-a/developed-neon-2/developed-neon-2_installation-and-operation-manual_753651006.webp)
6
Neon
- Conventional Fire Alarm Control Panel
2. Typing conventions and abbreviations
Throughout this manual specific symbols and character
types have special meaning. The following list summarizes
the typing conventions:
• [Button]:
A Keypad button that can be pressed.
• *Indicator*:
A visual indicator that may be lit or not.
e.g. *ALARM*.
The following terminology is used:
• PSU:
Power supply unit
• A.L.:
Access Level
• ALM:
Access Level Menu
• ALM.x.y.z:
Access Level Menu x, sub-item y, sub-item z.
• EOL:
End Of Line (device).
• AEOL:
Active End Of Line (device).
For indicators:
• OFF:
The indicator is disabled.
• ON:
The indicator is steady ON.
• BLINKING:
The indicator is alternating between ON
and OFF.
3. Installation
3.1 Installation checklist
*
Prepare the site: Make sure the installation location is
free from construction dust, debris, extreme tempera-
ture ranges and humidity.
*
Unpack the equipment
*
Install the cabinet: See ‘Installing the cabinet’ below
(section 3.2 ) for cabinet dimensions.
*
Install optional components
*
Review wire routing.
*
Connect the field wiring.
Care should be taken when connecting field wiring.
Do not make any connections with main or battery
power applied. The cabinet should be connected to a
suitable earth point at all times.
*
Check for opens, grounds, and shorts before connect-
ing.
*
Connect ground then AC power.
WARNING: Ensure that the building’s AC circuit
breaker is OFF before connecting high voltage wires
(230V AC) to the main connector.
*
Connect batteries.
*
Test for proper operation.
After a system power up, the user must perform an A.L.2
Reset to remove the System fault and enter normal
operational mode. This is by design
.
3.2 Installing the cabinet
Cabinets can be surface or flush mounted. See Figure 1
and Table 1 for framing and mounting dimensions.
To wall mount the cabinet:
1. Position the cabinet on the finished wall surface.
2. Fasten the cabinet to the wall surface where indicated.
Cabinet dimensions
Figure 1.
Neon cabinet dimensions
D1
40.5 cm
D2
7,5 cm
D3
29.6 cm
D4
38 cm
D5
22 cm
D6
23.5 cm
D7 [Ø]
0.5 cm
Table 1.
Framing and mounting dimensions
4. General Description
The
Neon
conventional fire alarm control panels have been
designed to provide full fire detection coverage to buildings
or installations that require fire detection systems of 2 to
8 zones.
There are three (3) basic models for the
Neon
panel:
Model
Zones
Siren Outputs
Neon 2
2
2
Neon 4
4
4
Neon 8
8
4
Table 2.
Neon panel models
Operating Voltage 230V AC / 50-60Hz.
The analytic indications and the simple controls of the
Neon
panel ensure the easy handling and controlling of the
system by the operator.
5. Keyboard Indications and Controls
Operating, monitoring and programming of the panel is
performed in three different access levels. In access level 1
only indicative operations are unlocked. Access to level 2 is
achieved by the keyswitch on the face of the panel (
Figure
2
) or the use of the A.L.2 PIN. Operations at access level 2
are performed with the keypad. Access level 3 operations
are accomplished with the micro switches on the main cir-
cuit board of the panel
(see section 8)
.