background image

10

Neon

 - Conventional Fire Alarm Control Panel 

5.3.16 General Fault indication (General Fault)

GENERAL FAULT

, indicates a problem in the system. It 

turns 

ON

 

(steady ON) 

in case of: 

• 

Zone wiring connection problems,

•  Signalling devices output wiring problems 

•  Relay outputs wiring problems. 

•  Auxiliary and power faults

•  Earth fault condition
The above mentioned problems could be open circuits, 

shorts between wires or shorts between wires and earth.
Consequently the Fault relay output is activated (

Item 22, 

page 4

). At the same time there will be a continuous audible 

notification from the on board Buzzer. 
It is possible to silence the Buzzer by pressing the 

SILENCE 

BUZZERS 

key 

[2]

, with the keyswitch in A.L.1 position.

When the problems causing the fault(s) are restored all the 

above indications will turn off automatically.

Short

Normal

Open

Min

Max

Min

Max

Min

Max

Signaling  

devices

0

400 1.6K

7K

10K

Zone

0

15

1.5K

7K

10K

Table 4.

 Fault detection values (Ohm)

Zones also recognize the range of 40 to 1200 Ohms as 

alarm.

5.3.17 Zone Disablements, Test, Fault indications

These indicators, referenced as FL1 to FL8, show that the 

corresponding zone is:

• 

In “zone open” Fault if blinking at 1 sec interval

• 

In “Zone Shorted“ fault if blinking at 0.5 sec interval.

•  Disabled by an A.L.2 operation, if continuously ON with 

the 

*DISABLEMENTS*

 indicator also active (steady 

ON).

•  In test (and thus disabled), if continuously ON with 

*TEST* 

indicator also active (steady ON).

Zone faults

Possible causes of a zone fault indication are: 

(a1)

 Disconnection or interruption of wiring of the zone.

(a2)

 Short-circuit in the wiring of the zone.

(a3)

 Removal of sensor from its base.

(a4)

 Removal of the terminating resistor or capacitor 

(EOL).

See also section 10.3

.

Watchdog System

The 

Neon

 panel contains a watchdog circuit that will ac-

tivate when the microprocessor is either faulty or unable 

to execute the programmed firmware. Upon detection, the 

Fault relay, the on board sounder and the system and gen-

eral fault indicators on the user interface are all activated.

6. Alarm Verification

(also called Intellizone in this manual)

6.1 System Overview - Alarm Verification

The purpose of the Alarm Verification feature is to minimize 

false alarms. The concept of alarm verification is to have 

the system receive a Second Alarm signal from the same 

or  another  zone  within  a  predefined  time  after  the  First 

Alarm signal. Only then will the General Alarm condition be 

activated. To prevent the First Alarm signal from causing a 

General Alarm, it must originate from an intellizone.
Please  note  that  the  terms Alarm  Verification  and  intelli

-

zone are treated as synonymous in the following sections.

6.2 System Operation - Alarm Verification

Each zone may be programmed to be an “Intellizone” (from 

microswitch SW-B). The sum of the intellizones form the 

intellizone group.
The operation of the intellizone system is as follows:
When an alarm condition is detected on an intellizone (First 

Alarm):
•  The 

“Intellizone Delay” 

is activated (can be set from 

SW-A 6,7,8).

• 

The “Automatic Alarm Cancel Delay” (5 minutes) timer 

is activated.

•  The pre-alarm is indicated on the corresponding Alarm 

Indicator  (AL1-AL8).  The  General  Alarm  Indicator  is 

not activated.

• 

The system buzzer produces a notification sound.

• 

The  Main  Siren  relays  are  NOT  activated  (General 

Alarm condition is not established).

• 

The Siren 2 relay, if configured so by SW-A-5, is acti

-

vated.

• 

After the “Intellizone Delay” time, the automatic detec

-

tors are reset.

• 

During  the  “Intellizone  Delay”  any  other  zone  (NOT 

only  intellizones)  except  the  initial  may  provide  the 

Second Alarm signal (see below).

• 

The  intellizone  pre-alarm  will  remain  active  for  the 

remainder of the 5 minutes before the initial alarm is 

completely canceled.

During the above delay (Automatic Alarm Cancel Delay) 

any zone (not only intellizones), including the initially trig

-

gered intellizone may provide the Second Alarm.

The Second Alarm will:
• 

Activate the General Alarm Condition.

•  Activate the alarm siren relays.

• 

De-activate  the  Siren  2  relay,  if  configured  for  pre-

alarms by SW-A-5.

The  Intellizone  feature  may  be  disabled/re-enabled  from 

Access Level 2, Key 

[3]

  “Alarm  verification  toggle”.  The 

system status is indicated accordingly with the “Alarm Veri-

fication” as below: 

•  OFF: 

No Alarm verification programmed.

•  ON:

 Alarm verification active for selected zones.

•  BLINKING:

 Alarm verification is programmed but not 

active at the moment, either due to Day/Night or man

-

ual disablement.

6.3 Day/Night hardware input

The disablement of the Alarm Verification system, can also 

be  controlled  by  the  “Day/Night  input”  hardware  input.  If 

left unused (nothing connected to the input) the system will  

use Alarm Verification, unless the user has disabled it.

If connected to a switch (for example to a periodic timer), 

when the contacts are closed (shorted together) the Alarm 

Verification is disabled. The panel will indicate the disabled 

condition by blinking the 

*ALARM VERIFICATION*

 indica-

tor.

Содержание DEVELOPED Neon 2

Страница 1: ...Installation and Operation Manual Conventional Fire Alarm Control Panel Version 1 Revision 4 ...

Страница 2: ... be responsible in any way whatsoever for faulty installation or connection Declaration of Conformity Fire alarm control panel NEON is certified from EVPU Noti fied body No 1293 according to European Regulation CPR 305 2011 with certification number Νο 1293 CPR 0604 of June 27 2018 Standards EN 54 2 1997 A1 2006 AC 1999 EN 54 4 1997 A2 2006 AC 1999 Certificates can be found online at phsvesis com ...

Страница 3: ...Level 2 Indication 9 5 3 14 General Fire Alarm Indication 9 5 3 15 Zone ALARM indications 9 5 3 16 General Fault indication General Fault 10 5 3 17 Zone Disablements Test Fault indications 10 6 Alarm Verification 10 6 1 System Overview Alarm Verification 10 6 2 System Operation Alarm Verification 10 6 3 Day Night hardware input 10 6 5 System Setup Zone assignment Intellizone 11 6 6 System Setup In...

Страница 4: ...emote reset input 15 Zone inputs 16 Batteries Secondary standby power source See sec tion 9 2 17 JP204 NO NC dry contacts operated during reset 18 AUX R Auxiliary power output interrupted during re set 24 V DC 1 A max for devices that need resetable power This output is fused 19 AUX Auxiliary power output 24 V DC 1 A max This output is fused 20 BELL Bell class change operation input See sec tion 5...

Страница 5: ...tion Terminal Mains Power Supply 230 V AC 50 60Hz 2 5A Fuse 1A 250V Slow blow Hardware Reset Button Fuse 5A 250V Slow blow Fuse 1 6A 250V Fast blow 1 2 Neon Panel Wiring diagram and information 4 7K Signaling device 24 V DC Active End Of Line Capacitor End Of Line Resistor Panic button Photoelectric detector Rate of Rise Heat detector 4 7K 22uF AEOL 1 End Of Line Device 2 Active End Of Line Device...

Страница 6: ...Connect batteries Test for proper operation After a system power up the user must perform an A L 2 Reset to remove the System fault and enter normal operational mode This is by design 3 2 Installing the cabinet Cabinets can be surface or flush mounted See Figure 1 and Table 1 for framing and mounting dimensions To wall mount the cabinet 1 Position the cabinet on the finished wall surface 2 Fasten ...

Страница 7: ... While key 4 is kept pressed the panel shows the configu ration related to the 4 Siren relay outputs Fault indicators FL1 FL8 Zones that will be de layed if triggered by an alarm are blinking Siren Indicators S1 to S4 Siren outputs that will be delayed are blinking Siren Indicator 2 S2 If allocated to Pre alarms is ON steady Key 6 Test On Normal press or while kept pressed all the visual indi cato...

Страница 8: ... the 3 second activation the panel performs a zone reset useful for automatic detec tors Any zone in this state is considered disabled and is so in dicated If any zone is in test mode the TEST indicator is illuminated Key 7 EVACUATION Long Press This operation requires Access level 2 if SW C 8 is set see section 8 3 key 7 above Key 8 RESET panel Exit A L 2 Long Press The reset operation will Remov...

Страница 9: ... 1 at least one zone is in testing mode steady on In access level 2 the system is in test selection zone mode blinking 5 3 8 Outputs Delay Indication The meaning of this indication is as below OFF No delays to outputs are active or programmed ON The system has programmed and active delays to outputs BLINKING The system has programmed delays to outputs but they are currently disabled with an Access...

Страница 10: ...Alarm signal Only then will the General Alarm condition be activated To prevent the First Alarm signal from causing a General Alarm it must originate from an intellizone Please note that the terms Alarm Verification and intelli zone are treated as synonymous in the following sections 6 2 System Operation Alarm Verification Each zone may be programmed to be an Intellizone from microswitch SW B The ...

Страница 11: ...outputs without delay called Im mediate Zones A group of outputs relays that will always activate without delay called Immediate Outputs A group of outputs relays that will activate with de lay if the Alarm is triggered by a Delayed zone called Delayed Outputs Additionally there is a predefined delay in access level 3 dip switches SW C 1 2 3 called Output Delay 7 2 System behavior The term Delayed...

Страница 12: ... the pair are indicated in alarm 8 1 2 System setup Zone inputs To enable the cross zoning function place the appropriate micro switches to the ON position according to Table 6 Ex ample switching SWA 1 to ON will activate cross zoning on zones 1 and 2 The two zones 1st and 2nd should be connected to the detectors that are installed in the pro tected area A common practice is to install different t...

Страница 13: ...current of the auxiliary out puts plus the siren outputs must not exceed 1 5 Amp The Alarm output also monitors the notification appliances wiring for open lines and short circuits The connection of a 4 7K Ohm EOL resistor is required as shown in below see section 1 2 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K Signaling device 24V DC Panic button Photoelectric detector Rate of Rise Heat detector Figu...

Страница 14: ...____ Zone 4 _______________________________________ Zone 5 _______________________________________ Zone 6 _______________________________________ Zone 7 _______________________________________ Zone 8 _______________________________________ Installed by Name Company Address Phone For service contact Company Address Phone Acceptance Inspection by Date DEVELOPED BY PARADOX HELLAS S A Korinthou 3 Meta...

Страница 15: ...mounting extruding depth 25mm Weight without the batteries 2 800gr Appendix B Calculations Battery calculation worksheet Use this worksheet to determine the minimum capacity required for the panel s standby battery You can obtain operating current re quirements for notification appliances from their respective installation sheets Standby Current mA Alarm Current mA Base panel 1 Aux current Detecto...

Страница 16: ...Document Part Number NEON PI01 CPR version 1 revision 4 12 2018 ...

Отзывы: