8
Neon
- Conventional Fire Alarm Control Panel
Any new alarm event will automatically cancel the silence.
If no sounders are active, the silence operation will only
momentarily activate the corresponding indicator.
Bell / Class change (Long Press)
While key
[2]
is kept pressed, the Sounders normally used
for Fire Alarms, are activated with a constant pattern. This
is typically used in schools to sound a class change.
Siren 2 output will not be used if allocated to the pre-
alarm function.
While the panel is in this mode, all indicators are turned off
and only the activated relay indicators (S1 to S4) are blink
-
ing every 0.25 seconds.
The panel returns to normal indication when the key is re-
leased.
Key [3]:
Alarm Verification Toggle
Only useful if the installation uses the Alarm Verification
functionality.
The Alarm Verification operation may be disabled and re-
enabled with successive presses of key
[3]
(see section
5.3.9 for indication).
The user may verify which zones (if any) belong to the
alarm verification group by pressing and holding key
[3]. While this key is kept pressed the *ALARM
VERIFICATION* indicator flashes at a slow rate while
blinking disablement indicators show the group
members (
see section 5, Alarm Verification
).
Key [4]: Output Delays Toggle
Only useful if the installation uses the “Output Delays”
feature.
The Output Delays operation may be disabled or re-en-
abled with successive presses of key
[4]
(see section 5.3.8
for indication).
Key [5]: ZONES Disablement
Used to selectively place zones in disabled mode. A dis
-
abled zone is fully ignored by the system in both faults and
alarms.
How to operate:
1.
Press Key
[5]:
*DISABLEMENTS*
indicator starts
blinking: the panel is in zone selection mode.
2.
Use keys
[1]
to
[8]
to toggle the disablement of the
corresponding zone.
3.
The
*Disablements | Test | Faults*
indicators show
any zones that are disabled (“steady on” state).
Panels with 2 or 4 zones will ignore the keys with no
corresponding zone.
Zone selection mode will be cancelled after 10 seconds
of user inactivity.
Disabling a zone in alarm will cancel the alarm state but will
not reset any automatic detectors that may have caused/
latched the alarm.
Key [6]: ZONES test
Used to place zones in the “Test” state. It is used for testing
the panel as well as any automatic detectors attached to
the zone of interest.
Any alarm condition detected from a zone in test will cause
the panel’s buzzer and the local Sirens (relays 1 to 4) to be
activated for 3 seconds. After the 3 second activation the
panel performs a zone reset (useful for automatic detec
-
tors).
Any zone in this state is considered disabled and is so in
-
dicated.
If any zone is in test mode, the
*TEST*
indicator is
illuminated.
Key [7]: EVACUATION (Long Press)
This operation requires Access level 2 if SW-C-8 is set
(see section 8.3 key [7], above).
Key [8]: RESET panel
Exit A.L.2 (Long Press)
The reset operation will:
•
Remove power from the zone circuits for 3 seconds,
resetting all automatic detectors.
• Restore all Outputs to their idle state.
• Cancel any pending pre-alarms.
•
Cancel all Alarm Verification timers (if active and run
-
ning).
• Cancel all faults including the startup System Fault.
“Remote Reset” Hardware input.
The remote reset input, if used, is connected to a
momentarily activating push-button (shorted while kept
pressed). This will cause the panel to do an Access Level
2 reset operation.
5.3 Indications
5.3.1 POWER Indication
The *
POWER*
indication is permanently ON if the main
power is present and batteries are healthy. This condition
signifies normal system operation.
*POWER*
indicator OFF signifies a total power failure of
the system. This can be due to a number of reasons. Some
of them are:
• Main power failure for an extended period of time during
which the batteries have been depleted.
• Blown main board fuse
(see section 1.1)
.
• Other malfunction of the power supply, main board
disconnected from PSU (power supply unit) etc.
Blinking power indicator signifies one of the following:
(a)
Removal or power loss of the batteries.
(b)
Main power loss.
1
(c)
Blown main power fuse or PSU fuse (see
section 1.1
).
In the above cases the on board buzzer sounds continu
-
ously.
1
The *
POWER SUPPLY FAULT*
indicator turns ON.
5.3.2 AUX POWER Fault Indication
When active, this indicator signifies that an overcurrent
condition at the auxiliary power outputs (section 1.1, items
18 & 19) is detected. The maximum allowed total current
for the two auxiliary outputs is 1 Amp. The panel is capa
-
ble of continuous operation even with a full short circuit at
these outputs. Please note that a short on any one of the
two outputs will disable both as well as any device powered
from them.
If more than 1 Amp is required, a compatible EN 54-4 ap
-
proved fire alarm power supply must be used. When such
a power supply is used, the negative output of the external
power supply must be connected to the negative terminal
of the AUX terminal (-AUX).
IMPORTANT: The total current of the auxiliary out-
puts plus the siren outputs must not exceed 1.5 Amp.
5.3.3 Battery Fault / Replace Indication
The Neon panel uses a battery fault detection system that
will generate a battery fault indication in the following cases: