![Paradox Hellas S.A. DEVELOPED Neon 2 Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/paradox-hellas-s-a/developed-neon-2/developed-neon-2_installation-and-operation-manual_753651011.webp)
11
Neon
- Conventional Fire Alarm Control Panel
This input may also be used with a manual external switch,
to provide an easier operation of the “Alarm Verification
Disable/enable” functionality.
6.4 System Setup - Zone connections - Intellizone
The system should have one or more zones connected to
automatic detectors. Manual call formats may also be con-
nected to intellizones but the alarm signal will be delayed
by the Intellizone Delay time.
6.5 System Setup - Zone assignment - Intellizone
To assign zones to the intellizone group set the required
corresponding microswitches on SW-B to ON (top posi-
tion).
Zones assigned to cross-zoning cannot be assigned to
the intellizone group. If both micro-switches are set, the
cross zone configuration takes precedence.
6.6 System Setup - Intellizone time delay
The Intellizone Delay can be set from the three micro
-
switches SW-A-6,7,8. The three switches form a binary
value from 0 to 7. Each unit corresponds to 10 seconds.
The table below summarizes the settings:
SW-A-6
SW-A-7
SW-A-8
Alarm Verification
OFF
OFF
OFF
No Alarm Verification
ON
OFF
OFF
10 sec
OFF
ON
OFF
20 sec
ON
ON
OFF
30 sec
OFF
OFF
ON
40 sec
ON
OFF
ON
50 sec
OFF
ON
ON
60 sec
ON
ON
ON
70 sec
Table 5.
Alarm Verification time set
IMPORTANT: To configure an EN54-2 compliant installation,
do not exceed 30 seconds of Intellizone delay time
.
7. Outputs delay operation
The Neon panel implements the “Output delays” fea-
ture as defined in the EN54-2 standards.
“Output delays” refers to the process of delaying the acti-
vation of an alarming output, after the system enters the
general fire alarm state.
Indications
The
*OUTPUTS DELAY*
indicator shows the status of the
system as below:
• OFF:
No output delays have been programmed.
• ON:
Output delays are in effect for selected outputs
(once an alarm occurs).
• BLINKING:
Output delays have been programmed but
are currently disabled due to user operation.
7.1 Operation Overview and operation
The system consists of the following:
•
A group of zones that, when trigger an Alarm event,
will activate some Siren outputs with delay (called “De-
layed Zones”).
•
A group of zones that, when trigger an Alarm event,
will activate all Siren outputs without delay (called “Im-
mediate Zones”)
• A group of outputs (relays) that will always activate
without delay (called “Immediate Outputs”)
• A group of outputs (relays) that will activate with de-
lay if the Alarm is triggered by a “Delayed zone”(called
“Delayed Outputs).
Additionally, there is a predefined delay in access level 3
(dip switches SW-C-1,2,3) called “Output Delay”.
7.2 System behavior
The term “Delayed Zone” is only meaningful in the con-
text of Delayed outputs. Even “Delayed Zones”, will ac-
tivate the General Fire Alarm without delay.
The following list describes the behavior of the output de-
lay system:
• As soon as an alarm event is triggered by an “Immedi-
ate Zone” all Siren output relays are activated imme
-
diately.
• As soon as an alarm event is triggered by a “Delayed
Zone”:
○
The timer of the output delays is started with “Out-
put Delay” time.
○
Siren output relays not in the “Delayed Outputs”
group are activated immediately.
○
Siren output relays in the “Delayed Outputs” group
are activated after the “Output Delay” time has
passed.
7.3 System setup - Dip switches - Delay and Zone al-
location
The dip switches SW-C-(1 to 5) define the operation and
options of the output delays as follows:
SW-C-1,2,3:
This is the binary value of the output delay.
An output delay of 0 means that no outputs are delayed. In
this case the rest of the switches are ignored. Delay time
other than 0 activates the output delays. Values are shown
below:
SW-C-1
SW-C-2
SW-C-3
Output Delays
OFF
OFF
OFF
No Output Delay
ON
OFF
OFF
1 min
OFF
ON
OFF
2 min
ON
ON
OFF
3 min
OFF
OFF
ON
4 min
ON
OFF
ON
5 min
OFF
ON
ON
6 min
ON
ON
ON
7 min
Table 6.
Outputs delay time set
SW-C-4:
Delayed Zone selection
This option defines if all or half of the available zones are
used as “Delayed Zones”.
0:
All available zones are “Delayed Zones”
1:
The first half zones are “Immediate Zones”
SW-C-5:
Delayed Outputs selection
The setting of this switch defines the Output relays that
form the “Delayed Outputs” group.
0:
Only outputs 3 and 4 (Siren3 and Siren4) are “Delayed
Outputs”.
1:
All 4 Siren relays are “Delayed Outputs”.
If Relay Output 2 is allocated to the pre-alarm feature, it
is not affected by the above operation.
8
. Access Level 3 - Panel Configuration
Settings in Access Level 3 can be performed via the mi
-
cro switches on the main board. This procedure must be
performed only by the installation engineer. On the main