Paradox Hellas S.A. DEVELOPED Neon 2 Скачать руководство пользователя страница 11

11

Neon

 - Conventional Fire Alarm Control Panel

This input may also be used with a manual external switch, 

to  provide  an  easier  operation  of  the  “Alarm  Verification 

Disable/enable” functionality.

6.4 System Setup - Zone connections - Intellizone

The system should have one or more zones connected to 

automatic detectors. Manual call formats may also be con-

nected to intellizones but the alarm signal will be delayed 

by the Intellizone Delay time.

6.5 System Setup - Zone assignment - Intellizone

To assign zones to the intellizone group set the required 

corresponding microswitches on SW-B to ON (top posi-

tion).

Zones assigned to cross-zoning cannot be assigned to 

the intellizone group. If both micro-switches are set, the 

cross zone configuration takes precedence. 

6.6 System Setup - Intellizone time delay

The  Intellizone  Delay  can  be  set  from  the  three  micro

-

switches  SW-A-6,7,8.  The  three  switches  form  a  binary 

value from 0 to 7. Each unit corresponds to 10 seconds. 
The table below summarizes the settings:

SW-A-6

SW-A-7

SW-A-8

Alarm Verification

OFF

OFF

OFF

No Alarm Verification

ON

OFF

OFF

10 sec

OFF

ON

OFF

20 sec

ON

ON

OFF

30 sec

OFF

OFF

ON

40 sec

ON

OFF

ON

50 sec

OFF

ON

ON

60 sec

ON

ON

ON

70 sec

Table 5.

 Alarm Verification time set

IMPORTANT: To configure an EN54-2 compliant installation, 

do not exceed 30 seconds of Intellizone delay time

.

 

7. Outputs delay operation

The Neon panel implements the “Output delays” fea-

ture as defined in the EN54-2 standards.

“Output delays” refers to the process of delaying the acti-

vation of an alarming output, after the system enters the 

general fire alarm state.

Indications

The 

*OUTPUTS DELAY*

 indicator shows the status of the 

system as below:

•  OFF:

 No output delays have been programmed.

•  ON:

  Output  delays  are  in  effect  for  selected  outputs 

(once an alarm occurs).

•  BLINKING:

 Output delays have been programmed but 

are currently disabled due to user operation.

7.1 Operation Overview and operation

The system consists of the following:
• 

A group of zones that, when trigger an Alarm event, 

will activate some Siren outputs with delay (called “De-

layed Zones”).

• 

A group of zones that, when trigger an Alarm event, 

will activate all Siren outputs without delay (called “Im-

mediate Zones”)

•  A group of outputs (relays) that will always activate 

without delay (called “Immediate Outputs”)

•  A group of outputs (relays) that will activate with de-

lay if the Alarm is triggered by a “Delayed zone”(called 

“Delayed Outputs).

Additionally, there is a predefined delay in access level 3 

(dip switches SW-C-1,2,3) called “Output Delay”.

7.2 System behavior

The term “Delayed Zone” is only meaningful in the con-

text of Delayed outputs. Even “Delayed Zones”, will ac-

tivate the General Fire Alarm without delay.

The following list describes the behavior of the output de-

lay system:
•  As soon as an alarm event is triggered by an “Immedi-

ate Zone” all Siren output relays are activated imme

-

diately.

•  As  soon  as  an alarm event is triggered by a “Delayed 

Zone”:

 

The timer of the output delays is started with “Out-

put Delay” time. 

 

Siren output relays not in the “Delayed Outputs” 

group are activated immediately.

 

Siren output relays in the “Delayed Outputs” group 

are activated after the “Output Delay” time has 

passed.

7.3 System setup - Dip switches - Delay and Zone al-

location

The dip switches SW-C-(1 to 5) define the operation and 

options of the output delays as follows:

SW-C-1,2,3:

 This is the binary value of the output delay. 

An output delay of 0 means that no outputs are delayed. In 

this case the rest of the switches are ignored. Delay time 

other than 0 activates the output delays. Values are shown 

below:

SW-C-1

SW-C-2

SW-C-3

Output Delays

OFF

OFF

OFF

No Output Delay

ON

OFF

OFF

1 min

OFF

ON

OFF

2 min

ON

ON

OFF

3 min

OFF

OFF

ON

4 min

ON

OFF

ON

5 min

OFF

ON

ON

6 min

ON

ON

ON

7 min

Table 6.

 Outputs delay time set

SW-C-4:

 Delayed Zone selection

This option defines if all or half of the available zones are 

used as “Delayed Zones”.

0:

 All available zones are “Delayed Zones”

1:

 The first half zones are “Immediate Zones”

SW-C-5:

 Delayed Outputs selection

The  setting  of  this  switch  defines  the  Output  relays  that 

form the “Delayed Outputs” group.

0:

 Only outputs 3 and 4 (Siren3 and Siren4) are “Delayed 

Outputs”.

1:

 All 4 Siren relays are “Delayed Outputs”.

If Relay Output 2 is allocated to the pre-alarm feature, it 

is not affected by the above operation.

 

8

. Access Level 3 - Panel Configuration 

Settings in Access Level 3 can be performed via the mi

-

cro switches on the main board. This procedure must be 

performed only by the installation engineer. On the main 

Содержание DEVELOPED Neon 2

Страница 1: ...Installation and Operation Manual Conventional Fire Alarm Control Panel Version 1 Revision 4 ...

Страница 2: ... be responsible in any way whatsoever for faulty installation or connection Declaration of Conformity Fire alarm control panel NEON is certified from EVPU Noti fied body No 1293 according to European Regulation CPR 305 2011 with certification number Νο 1293 CPR 0604 of June 27 2018 Standards EN 54 2 1997 A1 2006 AC 1999 EN 54 4 1997 A2 2006 AC 1999 Certificates can be found online at phsvesis com ...

Страница 3: ...Level 2 Indication 9 5 3 14 General Fire Alarm Indication 9 5 3 15 Zone ALARM indications 9 5 3 16 General Fault indication General Fault 10 5 3 17 Zone Disablements Test Fault indications 10 6 Alarm Verification 10 6 1 System Overview Alarm Verification 10 6 2 System Operation Alarm Verification 10 6 3 Day Night hardware input 10 6 5 System Setup Zone assignment Intellizone 11 6 6 System Setup In...

Страница 4: ...emote reset input 15 Zone inputs 16 Batteries Secondary standby power source See sec tion 9 2 17 JP204 NO NC dry contacts operated during reset 18 AUX R Auxiliary power output interrupted during re set 24 V DC 1 A max for devices that need resetable power This output is fused 19 AUX Auxiliary power output 24 V DC 1 A max This output is fused 20 BELL Bell class change operation input See sec tion 5...

Страница 5: ...tion Terminal Mains Power Supply 230 V AC 50 60Hz 2 5A Fuse 1A 250V Slow blow Hardware Reset Button Fuse 5A 250V Slow blow Fuse 1 6A 250V Fast blow 1 2 Neon Panel Wiring diagram and information 4 7K Signaling device 24 V DC Active End Of Line Capacitor End Of Line Resistor Panic button Photoelectric detector Rate of Rise Heat detector 4 7K 22uF AEOL 1 End Of Line Device 2 Active End Of Line Device...

Страница 6: ...Connect batteries Test for proper operation After a system power up the user must perform an A L 2 Reset to remove the System fault and enter normal operational mode This is by design 3 2 Installing the cabinet Cabinets can be surface or flush mounted See Figure 1 and Table 1 for framing and mounting dimensions To wall mount the cabinet 1 Position the cabinet on the finished wall surface 2 Fasten ...

Страница 7: ... While key 4 is kept pressed the panel shows the configu ration related to the 4 Siren relay outputs Fault indicators FL1 FL8 Zones that will be de layed if triggered by an alarm are blinking Siren Indicators S1 to S4 Siren outputs that will be delayed are blinking Siren Indicator 2 S2 If allocated to Pre alarms is ON steady Key 6 Test On Normal press or while kept pressed all the visual indi cato...

Страница 8: ... the 3 second activation the panel performs a zone reset useful for automatic detec tors Any zone in this state is considered disabled and is so in dicated If any zone is in test mode the TEST indicator is illuminated Key 7 EVACUATION Long Press This operation requires Access level 2 if SW C 8 is set see section 8 3 key 7 above Key 8 RESET panel Exit A L 2 Long Press The reset operation will Remov...

Страница 9: ... 1 at least one zone is in testing mode steady on In access level 2 the system is in test selection zone mode blinking 5 3 8 Outputs Delay Indication The meaning of this indication is as below OFF No delays to outputs are active or programmed ON The system has programmed and active delays to outputs BLINKING The system has programmed delays to outputs but they are currently disabled with an Access...

Страница 10: ...Alarm signal Only then will the General Alarm condition be activated To prevent the First Alarm signal from causing a General Alarm it must originate from an intellizone Please note that the terms Alarm Verification and intelli zone are treated as synonymous in the following sections 6 2 System Operation Alarm Verification Each zone may be programmed to be an Intellizone from microswitch SW B The ...

Страница 11: ...outputs without delay called Im mediate Zones A group of outputs relays that will always activate without delay called Immediate Outputs A group of outputs relays that will activate with de lay if the Alarm is triggered by a Delayed zone called Delayed Outputs Additionally there is a predefined delay in access level 3 dip switches SW C 1 2 3 called Output Delay 7 2 System behavior The term Delayed...

Страница 12: ... the pair are indicated in alarm 8 1 2 System setup Zone inputs To enable the cross zoning function place the appropriate micro switches to the ON position according to Table 6 Ex ample switching SWA 1 to ON will activate cross zoning on zones 1 and 2 The two zones 1st and 2nd should be connected to the detectors that are installed in the pro tected area A common practice is to install different t...

Страница 13: ...current of the auxiliary out puts plus the siren outputs must not exceed 1 5 Amp The Alarm output also monitors the notification appliances wiring for open lines and short circuits The connection of a 4 7K Ohm EOL resistor is required as shown in below see section 1 2 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K 4 7K Signaling device 24V DC Panic button Photoelectric detector Rate of Rise Heat detector Figu...

Страница 14: ...____ Zone 4 _______________________________________ Zone 5 _______________________________________ Zone 6 _______________________________________ Zone 7 _______________________________________ Zone 8 _______________________________________ Installed by Name Company Address Phone For service contact Company Address Phone Acceptance Inspection by Date DEVELOPED BY PARADOX HELLAS S A Korinthou 3 Meta...

Страница 15: ...mounting extruding depth 25mm Weight without the batteries 2 800gr Appendix B Calculations Battery calculation worksheet Use this worksheet to determine the minimum capacity required for the panel s standby battery You can obtain operating current re quirements for notification appliances from their respective installation sheets Standby Current mA Alarm Current mA Base panel 1 Aux current Detecto...

Страница 16: ...Document Part Number NEON PI01 CPR version 1 revision 4 12 2018 ...

Отзывы: