- Conventional Fire Alarm Control Panel
Appendix A:
Panel Specifications
Neon 2
Neon 4
Neon 8
Number of zones
2
4
8
Maximum number of detectors per zone
20
Notification appliances outputs (e.g. sirens)
2
4
4
Notification appliances current
4 x 400mA (total maximum current 1Amp)
Mains Power
230V AC 50/60Hz
Zones input voltage (with EOL & AEOL)
16 to 21 V
Maximum input power
100 VA max input power (0.5 Amp)
Battery placement
2 x 12V 7Ah VRLA batteries will fit in the panel
Standby Power
5 VA (25 mA)
Auxiliary power outputs
24V DC 1Amp total (‘AUX’ + ‘AUX R’)
Zone termination
4,7 KOhm 5% 1/2W resistors or 22uF / 25
V electrolytic capacitors
Monitored output termination
4,7 KOhm resistors
5% 1/2W
Fire relay output
Dry contacts NO or NC selectable.
50 V / 1.5 A max (DC or AC)
Fault relay output
Dry contacts NO or NC selectable.
50 V / 1.5 A max (DC or AC)
Environmental
Temperature: -2 to 45 °C (32 to 120 °F)
Humidity: 5 to 95% RH, non condensing
Panel’s dimensions (HxWxD) [mm]
315 x 425 x 105 mm. In semi flash wall mounting extruding depth: 25mm
Weight (without the batteries)
2.800gr
Appendix B:
Calculations
Battery calculation worksheet
Use this worksheet to determine the minimum capacity required for the panel’s standby battery. You can obtain operating current re
-
quirements for notification appliances from their respective installation sheets.
Standby
Current (mA)
Alarm
Current (mA)
Base panel
[1]
Aux current
Detector’s consumption
[3]
Total current
Required standby and alarm
time
x
Standby
time 24hr x
Alarm time
5 min = 0.083 hr
10 min = 0.167 hr
15 min = 0.250 hr
30 min = 0.500 hr
mAh +
mAh =
mAh
÷1000
Battery amp hour total =
Ah
x 1.2
Minimum battery size
[2]
=
Ah
[1] Base panel includes the main controller board with no load, only EOL resistors. Consumption on Standby mode: See Appendix A.
[2] The maximum battery size the panel can charge is 2x7 Ah 12 V.
[3] Use maximum value or actual calculated value from the Form below.
Zones detector’s consumption calculation
Zones
Quantity of Detectors
Detectors consumption
Total standby consumption
[4]
(quantity x consumption in mA)
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Total consumption for all zones =
[4] Maximum standby consumption per zone may not exceed
15
mA.