Chapter 4 Managing SNMP-NET
Running the Web Browser (Internet Explorer)
1. Make sure that you have a TCP/IP network already installed.
2. If there is no DHCP network service on the network, contact your network administrator to
get an IP address for you workstation that has the same network’s address as the
SNMP-NET IP address.
The
default IP address of SNMP-NET is 192.168.1.100.
3. Start your Web Browser. Enter the URL “http://host_name” or “http://ip_address” in the
address box. The SNMP-NET will then ask for your account and password, input the
correct account and password then the UPS management home page will be shown on the
screen.
Note:
SNMP-NET will logout the user automatically if there is no data transmission through
HTTP connection for more than 30 minutes.
Smart Shutdown
Initiates a signal for the server to shutdown. After the user-defined “Estimated OS Shutdown
Delay”, the output power is switched off. SNMP-NET Client or SNMP ShutdownAgent must be
used on the server for it to be properly shutdown. The “Estimated OS Shutdown Delay”
includes the assigned countdown delay in the shutdown software plus the duration of OS
shutdown process. When shutdown software receives the Smart Shutdown signal, the low
battery reaction settings will be used to process the shutdown procedure.
External Battery Pack
If you are using an External Battery Pack with this UPS, the UPS must be configured so that; the
UPS will report the correct estimated runtime and the Battery capacity bar graph LEDs will
display properly. External Battery Pack is located in the Configure folder.
UPS Shutdown Schedule
UPS only:
SNMP-NET device supports two kinds of shutdown schedules – (1) Weekly Schedule, (2)
Special Day Schedule. Set both of these options to plan your UPS schedule shutdown and
restart time.
UPS + Shutdown Software (SNMP-NET Client):
If your SNMP-NET device needs to work with the shutdown software to protect your servers,
which are powered by the UPS and you want to control the schedule shutdown and restart from
SNMP-NET device then go to the Configure page and enable the “Perform Smart Shutdown in
Schedule” option. You can also set the shutdown schedule using the shutdown software. And
because the shutdown software will send the control command to UPS through SNMP to
shutdown the UPS, we have to add the server IP address with write permission in the SNMP
Table of SNMP-NET device.
Note:
Before managing the UPS Shutdown Schedule, please make sure that the Date and
Time in SNMP-NET are correct.