background image

SynapSense

®

 2.4GHz Industrial Gateway 

Hardware Installation Manual

 

 

16 

Requirements

 

 

This chapter lists the hardware, software, tools, and additional material requirements for 
installing the Industrial Gateway in a data center or plant. 

 

 

Hardware

 

 

Industrial Gateway kit 

 

 

Software

 

 

Current version of MapSense™ software. 

 

Tools and Materials

 

 

 

The following list contains the minimum tool and material requirements installers need to 
bring to the job site. 

 

  Proper dress and shoes for performing work in a data center or plant  

                     (Including areas inside  the subfloor and in overhead plenums). 

  Ladder or step stool sufficient to reach all Gateway installation locations 

(typically placed well above the height of all server cabinets in their service 
radius) 

  Spare Industrial Gateway (if desired) 

  Laptop 

  3M Command Strips 

  Adhesive Cable Clips 

  Alcohol wipes 

  Drill and Bits (for Industrial Gateway Mounting Plate installations 

only) 

  Flashlight 

  Utility Knife 

  Screwdrivers 

  Label Maker 

  M12 Threaded Plastic Caps for Unused Gateway Connectors 

  This document and MapSense™ user guides. 

  Printed MapSense™ layout of the plant or data center showing cabinets and 

sensor installation locations 

 
Required Personal identification (driver’s license or passport) to present to security 
personnel 

 
 

 

 

Содержание SynapSense 1167

Страница 1: ...SynapSense 2 4GHz Industrial Gateway Model 1167 Installation Use Manual ...

Страница 2: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 2 Release 0v6 Issue 1 ...

Страница 3: ...ucts for use in such applications do so at their own risk and agree to fully indemnify and hold Panduit and its officers employees subsidiaries affiliates and distributors harmless against all claims costs damages and expenses and reasonable attorney fees arising out of directly or indirectly any claim of personal injury or death associated with such unintended or unauthorized use even if such cla...

Страница 4: ...nt This equipment has been tested and found to comply with the limits of the European Council Directive on the approximation of the law of the member states relating to electromagnetic compatibility 2014 30 EU according to EN 55022 Class B This equipment has also been tested and found to comply with Radio Equipment Directive 2014 53 EU This equipment complies with the RoHS2 Directive 2011 65 EU wi...

Страница 5: ...ponsible for any incidental or consequential damages or for any loss arising in connection with the use or inability to use this product Some states provinces do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty excludes defects or damage due to misuse abuse or neglect This warranty gives you specifi...

Страница 6: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 6 ...

Страница 7: ...ures 17 General Installation Guidelines 17 Installation Preparations 19 Industrial Gateway Installation 19 Configure IndustrialGateway 20 Mount Industrial Gateway 22 Final Installation Activities 26 InstallationInspection 27 General Inspection 27 Inspect Operationand InstallationAppearance 27 EtherNet IP Configuration 27 Integration in PLC via EtherNet IP 28 Specifications 31 Appendix A Industrial...

Страница 8: ...hapter provides the scope overview application and block diagrams and kit components for installing and configuring an Industrial Gateways in a plant or data center Requirements This chapter lists the hardware software tools and additional material requirements for installing Industrial Gateways Installation Procedures This chapter describes general guidelines and specific procedures for configuri...

Страница 9: ...ventions escription his style is used for anything a user types cli taps The style also highlights SynapSense or example Click OK xceptions to the rule and other important inform t off with this note style prefix yellow exclamation mark icon denotes a war w electrical icon denotes a safety warning of a electrical nature section affect the overall activities in this docu user specific information o...

Страница 10: ...lle Le respect des avertissements et des précautions peut entraîner des blessures l équipement ce qui peut annuler la garantie L installation de cet équipement doit être conforme aux codes électriques locaux et Les espaces industriels peuvent présenter un risque de perte auditive Utilisez ropriée avant d entrer dans des zones à fort bruit Ne touchez aucun équipement électrique sans l approbation d...

Страница 11: ...1 2 Issues Americas 1 866 721 5302 x86810 during normal Central Standard Time business hours EMEA 44 1291 674 661 x22761 during normal U K business hours APAC 65 8200 3931 or 65 8200 3932 between 8 a m and 5 p m local time Severity 3 4 Issues Email normal business hours systemsupport panduit com ...

Страница 12: ... plant or data center For example usingSynapSense ThermaNode environmental sensors data can be acquired across the entire active area of the plant or data center The Model 1167 Industrial Gateway is powered by either a dedicated 24VDC nominal power supply 10 30Vdcmax or an IEEE 802 3af Power over Ethernet POE compatible network source Both power supply connections are designed to provide the user ...

Страница 13: ...4GHz Industrial Gateway Installation Manual 13 SynapSense 2 4GHz Industrial Gateway Kit The Industrial Gateway Kit contains the following components 1 ea SynapSense 2 4GHz Industrial Gateway Part Number 100 1167 001 ...

Страница 14: ...apSense 2 4GHz Industrial Gateway Hardware Installation Manual 14 1 ea 2 4GHz Dipole Antenna IP 67Rated LSR Part Number 001 0010 1 ea M12 4 5 Plug Cable 3meter A Coded To Connect 10 30Vdc Power to Gateway ...

Страница 15: ... The following components are available as additional options for the Industrial Gateway Industrial Gateway Mounting Plate optional accessory Allows Mounting of the Industrial Gateway to DIN rail using Std Clip Industrial Gateway T Mount Feet optional accessory ...

Страница 16: ...luding areas inside the subfloor and in overhead plenums Ladder orstep stool sufficientto reach all Gateway installation locations typically placed well above the height of all server cabinets in their service radius Spare Industrial Gateway if desired Laptop 3M Command Strips Adhesive Cable Clips Alcoholwipes Drill and Bits forIndustrial Gateway Mounting Plate installations only Flashlight Utilit...

Страница 17: ...teway Industrial Gatewayinstallationsshouldnotbe inareaswhereconcretewalls supportpillars largecablebundles airducting orothermetalenclosuresthat can block the wireless signal transmission to the sensors If a wireless line of sight obstruction is immovable the external dipole Antenna of the Industrial Gateway can be extended by up to 50 ft by using coaxial extension cable rated for 2 5GHz frequenc...

Страница 18: ...SynapSense 2 4GHz Industrial Gateway Hardware Installation Manual 18 ...

Страница 19: ...es before connecting Industrial Gateway to power source Use a PoE camera or other PoE device to test PoE source power to be connected to the Industrial Gateway Verify Static IP Verify the plant or data center IT provided one static IP address per Industrial Gateway Plan and Verify Ethernet Connection Verify the plant or data center provided one Ethernet cable connection per Industrial Gateway near...

Страница 20: ...ateway and wait for Gateway to Boot 2 Plug the M12 D coded Ethernet cable into the configuration port of the Industrial Gateway 3 The other end of the Ethernet cable should be plugged into the PC By default the configuration port of the Gateway will be running DHCP 4 Using the PC s web browser navigate to the Gateway s User Interface UI i e the Gateway s configuration web page located by typing 19...

Страница 21: ...o the configuration port of the next Industrial Gateway device to be configured 3 Repeat the activities in the previous table for each Industrial Gateway to be installed 4 Once all Industrial gateways are configured and verified close the Remote Gateway Manager logout option or exit the browser window 5 Verify all M12 IP67 Caps are installed in all unused connectors of the Industrial Gateway and o...

Страница 22: ... 3 Connect the M12 A coded Male Plug cable to the Industrial Gateway and the 10 30Vdc designated power supply if using the local 10 30Vdc power option of the Gateway 4 Connect the designated M12 D coded Ethernet Cable originating from a PLC or server assigned by the plant or data center s IT department to the Industrial Gateway 5 Apply Power to Gateway either by PoE or 10 30Vdc Power Supply Radio ...

Страница 23: ... Remove adhesive covers from the Command Strips on the back of the Industrial Gateway 10 Mount the Industrial Gateway onto an alcohol cleaned surface Press firmly for 30 seconds 11 Secure and route power cable and Ethernet Cable using adhesive Cable Clips Repeat previous steps for remaining Industrial Gateways to be installed When all Industrial Gateways are installed proceed to the Final Installa...

Страница 24: ...e allows the Industrial Gateway to be attached to standard DIN rail with a standard DIN rail clip A standard DIN rail clip is included with the Mounting Plate NOTE The installation instructions of the DIN Rail Mounting Plate to the Industrial Gateway are included with the optional DIN Rail Industrial Gateway Mounting Plate ...

Страница 25: ...t is attached to the corner of the Gateway using 1 of the included screws at the T center hole of the T Mount foot The foot screw is inserted from inside the lid of the Industrial Gateway at each corner access hole of the Gateway The T Mount holes can then be used to mark the hole locations on the wall or Plate if the Industrial Gateway is temporarily held at the installation location ...

Страница 26: ...le 6 to complete the activities for the Industrial Gateway installation Table 6 Final Installation Activities Activity Steps Clear Installation Area Clean installation area of debris pack aging etc Dispose of trash appropriately Proceed to Installation Inspection ...

Страница 27: ...reas in which there is a clear line of sight for wireless sensor s radio transmissions 3 Verify Ethernet cables and power wires if needed are secured EtherNet IP Configuration The Industrial WSN Gateway can act as an EtherNet IP adapter and provide the data of connected nodes via EtherNet IP To do this the Industrial WSN Gateway can establish up to 10 data transfer connections with 10 sensor nodes...

Страница 28: ...clicking under Ethernet in the design tree on the left side of the screen 3 Double click on the Industrial Gateway in the design tree on the left side of the screen to modify the properties of it a Create a unique name for the gateway NewGW in example screen shown below b Enter the IP address of the Industrial Gateway in the Ethernet Address area of the General tab 4 Click on the Sensor Config tab...

Страница 29: ...29 Once the nodes are running data can be viewed in the Device Map tab ...

Страница 30: ...way I1 N1 SensorType Decimal SINT Gateway I1 N1 Status Decimal SINT Gateway I1 N1 TimeStamp Gateway I1 N1 BatteryLife Decimal SINT Gateway I1 N1 Value1 Float REAL EZH Temp Gateway I1 N1 Value2 Float REAL EZH Humidity Gateway I1 N1 Value3 Float REAL Or name from SS Gateway I1 N1 Value4 Float REAL Gateway I1 N1 Value5 Float REAL Gateway I1 N1 Value6 Float REAL Gateway I1 N1 Value7 Float REAL Gateway...

Страница 31: ...e integrated into a different control system by using an Electronic Data Sheet EDS The EDS file is used by the network configuration tools to help identify and commission a product on a network The EDS file can be exported out of the SynapSoft application For more information on how to install an EDS file and integrate a new device see the corresponding documentation of your control system vendor ...

Страница 32: ...munity IEC 61131 2 2007 Edition 3 0 IEC 61000 4 6 Edition 4 0 2013 10Vrms with 1kHz sine wave 80 AM from 150kHz to 80MHz Power Ports M12 Local Power A Coded Port Pinout CIP Networks Library Volume 1 edition 3 13 Input voltage 10 30VDC maximum continuous Voltage at port Worry Free Polarity Connection Current draw 150mA 24VDC nominal no PoE supply M12 Data Port D Coded Power over Ethernet PoE M12 D ...

Страница 33: ...33 UL Approval UL 61010 1 UL61010 2 201 RED IEEE 802 15 4 Wireless Link 2405MHz 2480MHz 10dBm conducted TX power maximum ...

Страница 34: ...n the top lid of the Gateway as shown below Table7 shows the LED Status color definitions after the Industrial Gateway has booted and has reached its steady state operating condition 60 seconds Table 7 Industrial Gateway LED Definitions Eth Indicator Status Description Status Green Industrial WSN Gateway is functioning normally Red Industrial WSN Gateway has experienced a fault LED Off All Power i...

Страница 35: ...er via Ethernet Data Port i e via a remote PoE enabled Network Switch Off Gateway is not receiving remote voltage via PoE Power Green Local 24 VDC nominal power supply is ON Off Local power source is not connected to M12 or is powered OFF Red Wireless sensor network or configuration error Green Wireless sensor network operating normally Blue Flash IEEE 802 15 4 Wireless Packet Transmission Active ...

Страница 36: ...36 ...

Страница 37: ...dot notation for example 255 255 255 0 It is now in slash notation for example 24 The chart below shows both types of notation The CIDR Prefix is the new way the Subnet Mask is represented in the Industrial Gateway The most common notation value is 24 Table 8 Subnet Mask CIDR Subnet Mask CIDR Pre Total IPs Usable IPs Number of Class C Net works 255 255 255 255 32 1 1 1 256 255 255 255 254 31 2 0 1...

Страница 38: ...576 240 0 0 0 4 268 435 456 268 435 454 2 097 152 224 0 0 0 3 536 870 912 536 870 910 4 194 304 192 0 0 0 2 1 073 741 824 1 073 741 822 8 388 608 128 0 0 0 1 2 147 483 648 2 147 483 646 16 777 216 0 0 0 0 0 4 294 967 296 4 294 967 294 33 554 432 Changing the Industrial Gateway IP Address 1 Perform the activities configuration in Table4 Industrial Gateway Configuration 2 Change the laptop Host IP A...

Страница 39: ...CT LED will be blinking also when powered Setting Time Master Failed message in dm log file Not an Industrial WSN Gateway issue Issue Ping to Industrial Gateway Does Gateway respond No Server and Industrial WSN Gateway are not on the same subnet IP network address or subnet mask not configured correctly during configuration Web Login successful to Industrial Gateway home page at Port 80 from serve...

Страница 40: ...e See next test Is the Industrial Gateway radio in Diagnostic Mode Both STATUS and Ant LEDs are flashing Yes Reset Industrial Gateway by removing M12 RESET Cap and pressing RESET or Turn Off the Industrial Gateway to reset Gateway Recheck LEDs for Diagnostic Mode Re install M12 RESET cap Does Industrial WSN Gateway intermittently disconnect from the system Link Status shows as yellow and returns t...

Отзывы: