MR-REF & MR-REF3 Technical Manual
Issue 3, November 2013
2. Technical Specification.
Power Supply.
A
UXILIARY
P
OWER
S
UPPLY
&
L
OW
V
OLTAGE
P
OWER
S
UPPLY
AC Nominal
Range 80 – 265V AC / DC
Range 24V AC / 24-48V DC (Low Voltage Power Supply Optional Extra)
Frequency
45 - 65 Hz
Maximum Power Consumption
10VA, 15VA Nominal
Measurement.
R
ESTRICTED
E
ARTH
P
HASE
C
URRENT
M
EASUREMENT
Method
True RMS, Sample time <1ms
Range
1.0 to 200% E/F CT Primary Amps
Full Scale
200% E/F CT Primary Amps Setting
Display Accuracy
±
3% of Reading Over Range
Pick Up accuracy
±
3% of setting
Protection Functions.
E
ARTH
F
AULT
T
IME
D
ELAY
Earth Fault Trip
0.05 sec. for less than 1 second
Total Run Time
Accuracy
±
2%
T
IME
D
ELAYS
Accuracy
±
0.04 seconds
Exceptions
Earth Fault Trip
+40mS,-0.0@ 1.1 x setting
+30mS,-0.0@ 2 x setting
+20mS,-0.0@ 5 x setting
Total Run Time
Accuracy
±
2%
Relay Contacts Ratings.
O
UTPUT
R
ELAYS
Rated Load
10A @ 250 AC
10A @
30V DC
Maximum Breaking Voltage
250V AC
Max Making Current (max. 4s at duty cycle 10%)
35A
Max Breaking Capacity AC
2500VA
Max Breaking Capacity DC
600mA @ 110V DC
100mA @ 220V DC