6.7. Protect Settings.
This menu allows the user to configure all of the
protective functions.
DISPLAYED:
FULL DETAIL:
REF
Restricted Earth Fault
Ser Tmout
Serial Timeout
Intnl Err
Internal Error
Each function can be set to Alarm and / or Trip and / or Block or left as an unused function, disabled. The resets for
each are protective function are independently configurable as are the trip levels and trip times.
The protective function actions are as follows:
Disabled
Protection Disabled
Alarm
Alarm Enabled
Trip
Trip Enabled
Alarm & Trip
Alarm & Trip Enabled
Block
Block Enabled
Alrm & Blck
Alarm & Block Enabled
Trip & Blck
Trip & Block Enabled
A&T&B
Alarm, Trip and Block Enabled
The reset options are as follows;
Using the UP and DOWN keys the data can be
changed to one of the following;
Panel
Panel reset only
Serial
Serial reset only
S P
Serial or Panel reset
Remote
Remote reset only
R P
Remote or Panel reset
R S
Remote or Serial reset
R S P
Remote or Serial or Panel reset
AUTO
Auto reset
Each protection function is configurable independently of the others. The available action, the type of reset, the
various threshold levels and trip timers for each and every protection function can be found in
section 8.
This section describes in detail what each function does and how it operates.