Page 10
MR-REF & MR-REF3 Technical Manual
Issue 3, November 2013
6.2. Display Scroll.
Examples of the Display Scroll screens.
The <UP> and<DOWN> buttons will allow each of the above screens to be displayed in turn returning to the first
screen and will loop continuously.
If a threshold is breached then the phase pick-up and function description will appear to the right hand portion of the
display. The lower half right hand side of the display will show which protective element has started to operate, <E/F
PKUP>.
If the relay pick-ups the right hand LED will pulse red at approximately once per second. If the relay picks up on a
high set function the same LED will pulse at a faster rate, flashing at approximately three times per second
Should the threshold breach(s) clear before the alarm or trip timers have expired then the message will
automatically clear and the LED will revert to its previous indication.
If a fault has occurred and subsequently cleared, then providing a panel reset has been configured the reset prompt
will appear in the lower portion of the display to the right hand side, displayed as <RST>.
Selecting the <MENU> button allows access in to the sub menu and settings structure. The <UP> and <DOWN>
buttons scroll through each sub menu heading.
The left button selects entry to each level. The right button <TOP> restores the screen to the display scroll and
menu prompt.
Iref 0.00A Hlth
MENU
DI1
OFF
MENU
DI2
OFF
MENU
Tr Restricted EF
MENU RST
Al No Alarm
MENU
Feeder Settings
Y
Top
Serial Settings
Y
Top
Iref 0.00A Hlth
MENU