CAUTION
10.
Power supply connection to Indoor Unit.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
Must follow local national wiring standard, regulation and this installation instruction.
Strongly recommended to make permanent connection to a circuit breaker.
-
Power supply 1: Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0 mm.
-
Power supply 2: Use approved 15/16A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. (Only applicable for
S*C09*3E8)
or
Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0mm. (Only applicable for
S*C12*9E8/S*C16*9E8)
11. Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire.
12.
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other
properties.
13.
Installation work.
It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried
by one person.