51
12.1.7 Outdoor Fan Motor Operation
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it
stops 30 seconds after compressor stops operation.
12.2 Water
Pump
12.2.1 Water Pump Control
Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes.
However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the
compressor should be OFF immediately and restart delay after 3 minutes.
The system will start checking on the water flow level after operation start for 9 minutes. If water flow level is
detected low continuously for 10 secs, the water pump and compressor will be OFF permanently and OFF/ON
control panel LED will blink (H62 error occurs).
When error happen, the power has to be reset to clear the error.
If there is no error indication, the water pump shall be continuously running.
The water pump will remain ON when compressor OFF due to thermostat OFF setting is reached.
Pump ON-OFF control
a. During operation OFF or water pump stop at Tank Mode
b. During ERROR stop
c. Water flowing flag = ON
d. Outdoor air temperature < 30°C
When above [(a) or (b)] and (c) and (d) conditions fulfilled,
PUMP ON for 4 minutes, and OFF for 55 minutes continuously
When any of below mentioned condition below is achieved, this control is cancelled
f.
Operation = ON (except during water pump stop at tank mode)
g. Water pump run at tank mode
h. Change from tank mode to another mode during water pump stop at tank mode
i.
Outdoor air temperature
≥
32°C
j.
Water inlet temperature < 38°C for 30 minutes continuously
Содержание WH-SHF09D3E8
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up the Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram ...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E8 ...
Страница 22: ...22 8 1 2 WH SHF12D9E8 ...
Страница 23: ...23 8 2 Outdoor Unit ...
Страница 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E8 ...
Страница 25: ...25 9 1 2 WH SHF12D9E8 ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 30: ...30 10 2 2 Noise Filter Printed Circuit Board ...
Страница 42: ...42 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 59: ...59 ...
Страница 108: ...108 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 109: ...109 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UH09DE8 WH UH12DE8 ...
Страница 117: ...117 ...