64
14. Servicing
Mode
14.1 How to Take Out Front Plate
Please follow the steps below for take out front plate. Before removing the front plate of indoor unit, always
switch off all power supply (i.e. indoor unit power supply, heater power supply and tank unit power supply).
1 Remove the 2 mounting screws which located at bottom of the front plate and 1 mounting screw at the front
of the plate.
2 Gently pull the lower section of the front plate towards you to remove the front plate from left and right hooks.
3 Hold the left edge and right edge of front plate to lift up front plate from hooks.
14.2 How to Take Out Side Cabinet
Please follow the steps below to remove the side
cabinet. Before removing the front plate of indoor
unit always switch off all power supply (i.e. indoor
power supply, heater power supply and tank unit
power supply).
1 Perform the steps in HOW TO TAKE OUT
FRONT PLATE.
2 Remove all the 13 mounting screws on the left,
right and top of the side cabinet.
3 Gently remove the side cabinet by holding
both of the handles.
14.3 Test
Run
1 Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation
instruction.
2 Set ON to the indoor unit and RCCB/ELCB. Then, for control panel’s operation please refers to air-to-water
heatpump’s operation instruction.
3 For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.3 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If
adjust water pump speed cannot solve the problem, contact your local authorized dealer.
4 After test run, please clean the external filter. Reinstall it after finish cleaning.
14.4 Proper Pump Down Procedure
Strictly follow the steps below for proper pump down procedure. Explosion may occur if the steps are not
followed as per sequence.
1 Press the “SERVICE” switch on control panel to enter SERVICE mode. Operate the system in Sr :
01 mode for pump down operation.
2 After 10~15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10°C)), fully close
2 way valve.
3 After 3 minutes, fully close 3 way valve.
4 Press the “OFF/ON” switch on control panel to stop pump down operation.
5 Remove the refrigerant piping.
Содержание WH-SHF09D3E8
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up the Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram ...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E8 ...
Страница 22: ...22 8 1 2 WH SHF12D9E8 ...
Страница 23: ...23 8 2 Outdoor Unit ...
Страница 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E8 ...
Страница 25: ...25 9 1 2 WH SHF12D9E8 ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 30: ...30 10 2 2 Noise Filter Printed Circuit Board ...
Страница 42: ...42 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 59: ...59 ...
Страница 108: ...108 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 109: ...109 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UH09DE8 WH UH12DE8 ...
Страница 117: ...117 ...