44
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [60
°
C] whichever lower
Heat Pump Water Outlet set temperature is set to [63
°
C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[-2°C]
Case 1:
o
THERMO OFF TEMP:
1.
THERMO OFF TEMP = Heat pump tank target tempe
[0
°
C]
.
2.
Tank temperature > THERMO OFF TEMP for continuous 10 seconds after compressor off, switch 3
ways valve to room side.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-2
°
C]
or
2.
If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Case 2:
o
Heat pump THERMO OFF TEMP:
1.
Heat pump THERMO OFF TEMP = 63°C +
[+4
°
C]
.
2.
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet when heat pump THERMO OFF +
[-3
°
C]
.
2.
If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Case 3:
o
Heat pump THERMO OFF TEMP:
1.
Water inlet temperature > 65°C for continuous 60 secs, heat pump OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet temperature < 65°C.
2.
If water inlet temperature < THERMO ON TEMP AND External Room Thermo OFF, heat pump ON.
Case 4: (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON and switch 3 ways valve to room side
o
THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-2
°
C]
.
2.
If tank temperature < THERMO ON TEMP AND External Room Thermo OFF
AND
Solar 3WV OFF,
switch to tank side.
3 Backup Heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation
o
During External Room Thermo OFF time, Backup heater OFF
4 Booster heater control:
o
Booster heater On/Off follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
Содержание WH-SHF09D3E8
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up the Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram ...
Страница 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E8 ...
Страница 22: ...22 8 1 2 WH SHF12D9E8 ...
Страница 23: ...23 8 2 Outdoor Unit ...
Страница 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E8 ...
Страница 25: ...25 9 1 2 WH SHF12D9E8 ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 30: ...30 10 2 2 Noise Filter Printed Circuit Board ...
Страница 42: ...42 ...
Страница 48: ...48 ...
Страница 49: ...49 ...
Страница 59: ...59 ...
Страница 108: ...108 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 109: ...109 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UH09DE8 WH UH12DE8 ...
Страница 117: ...117 ...