13.3 Protection Control for Cooling Operation
13.3.1 Outdoor Air Temperature Control
The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor
frequency will adjust base on outdoor air temperature.
13.3.2 Freeze Prevention Control 1
1 When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will
stop operating.
2 Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C.
3 Indoor heat exchanger freeze prevention (H99) will memory in error history.
Содержание WH-SDC03E3E5 Series
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 4 1 2 Weekly Timer Setting ...
Страница 16: ...16 4 1 3 Setting Up the Special Functions ...
Страница 17: ...17 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 18: ...18 5 Dimensions 5 1 Indoor Unit ...
Страница 19: ...19 5 2 Outdoor Unit ...
Страница 21: ...21 ...
Страница 22: ...22 7 Block Diagram ...
Страница 23: ...23 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 43: ...43 ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 60: ...60 ...
Страница 110: ...110 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 111: ...111 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 123: ...123 18 4 Hydraulic Pump Performance ...