45
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [51°C] whichever lower
Heat Pump Water Outlet set temperature is set to [55°C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[55°C]
Case 1:
o
THERMO OFF TEMP:
1. THERMO OFF TEMP = Heat pump tank target tempe
[0°C]
.
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after compressor off, switch 3
ways valve to room side.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe
[-2°C]
or
2. If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Case 2:
o
Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 55°C +
[+2°C]
.
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet when heat pump THERMO OFF +
[-3°C]
.
2. If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Case 3:
o
Heat pump THERMO OFF TEMP:
1. Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
o
Next THERMO ON TEMP:
1. THERMO ON TEMP = Water inlet temperature < 55°C.
2. If water inlet temperature < THERMO ON TEMP AND External Room Thermo OFF, heat pump ON.
Case 4: (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON and switch 3 ways valve to room side.
o
THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe
[-2°C]
.
2. If tank temperature < THERMO ON TEMP AND External Room Thermo OFF
AND
Solar 3WV OFF,
switch to tank side.
3 Backup Heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation.
o
During External Room Thermo OFF time, Backup heater OFF.
4 Booster heater control:
o
Booster heater On/Off follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
Содержание WH-SDC03E3E5 Series
Страница 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 13: ...13 ...
Страница 14: ...14 ...
Страница 15: ...15 4 1 2 Weekly Timer Setting ...
Страница 16: ...16 4 1 3 Setting Up the Special Functions ...
Страница 17: ...17 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 18: ...18 5 Dimensions 5 1 Indoor Unit ...
Страница 19: ...19 5 2 Outdoor Unit ...
Страница 21: ...21 ...
Страница 22: ...22 7 Block Diagram ...
Страница 23: ...23 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 26: ...26 9 2 Outdoor Unit ...
Страница 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Страница 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 43: ...43 ...
Страница 49: ...49 ...
Страница 50: ...50 ...
Страница 60: ...60 ...
Страница 110: ...110 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 111: ...111 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 123: ...123 18 4 Hydraulic Pump Performance ...