39
5. Receiver shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table for details. Receiver’s cable
must be (4 or 3
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene sheathed cable. (connection
refer to Diagram 4.2).
6. Tank OLP’s cable must be (2
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene sheathed cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal no.13 and 14.
7. Tank Sensor shall be resistance type, please refer to Graph 4.1 for the characteristic and details of sensor. Its cable shall be
(2
×
min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-sheathed or polychloroprene sheathed
cable.
8. External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to Diagram 4.3). Its
cable must be (2
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no.17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
9. Solar Three-way Valve’s cable shall be (3
×
min 0.5 mm
2
), double insulation layer PVC-sheathed or polychloroprene sheathed
cable.
10. Must install Solar Connection PCB (optional) to Mono bloc unit when Solar Pump Station is utilized. Refer Solar
Connection PCB’s installation instruction for detail of installation.
11. Solar Pump Station’s cable shall be (2
×
min 0.5 mm
2
), of double insulation PVC-sheathed or polychloroprene sheathed
cable. Strongly recommended install with maximum length of 10 meter only.
11.4.1. Wire Stripping And Connecting Requirement
11.4.2. Connecting Requirement
For WH-MXF09D3E5:
• The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S
sc
is greater than or
equal to 817.851kW (for WH-MXF09D3E5) at the interface point between the user’s supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with a short-circuit power S
sc
greater than or equal to 817.851kW.
• The equipment’s power supply 1 shall be connected to a suitable supply network, having service current capacity
≥
100A per
phase. Please liaise with supply authority to ensure that the service current capacity at the interface point is sufficient for the
Terminal screw
Tightening torque N•cm {kgf•cm}
M4
157~196 {16~20}
M5
196~245 {20~25}
Содержание WH-MXF09D3E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Monobloc Unit ...
Страница 11: ...11 4 1 1 Main Components ...
Страница 13: ...13 ...
Страница 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Страница 16: ...16 4 1 6 Weekly Timer Setting ...
Страница 17: ...17 5 Dimensions 5 1 Monobloc Unit ...
Страница 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH MXF09D3E5 ...
Страница 21: ...21 7 2 WH MXF12D6E5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E5 ...
Страница 23: ...23 ...
Страница 24: ...24 8 2 WH MXF12D6E5 ...
Страница 25: ...25 ...
Страница 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E5 ...
Страница 27: ...27 ...
Страница 28: ...28 9 2 WH MXF12D6E5 ...
Страница 29: ...29 ...
Страница 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Страница 32: ...32 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 33: ...33 10 2 1 1 Capacitor Printed Circuit Board 10 2 1 2 Noise Filter Printed Circuit Board ...
Страница 34: ...34 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 103: ...103 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 109: ...109 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Страница 110: ...110 ...
Страница 114: ...114 19 2 Water System ...