14. Servicing
Mode
14.1 Test Run
1 Fill up the Tank Unit with water. For details refer to Tank Unit installation instruction and operation instruction.
2 Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient
temperatures is low. Recommended antifreeze:
Propylene glycol: 40% (equivalent to -20°C)
3 Set ON to the Mono bloc unit and RCCB. Then, for remote control operation please refers to (Mono bloc) Air-
to-Water Heatpump’s operation instruction.
4 For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.3 MPa. If necessary,
adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water
pump speed cannot solve the problem, contact your local authorized dealer.
5 After test run, please clean the external filter. Reinstall it after finish cleaning.
14.2 Proper Pump Down Procedure
Strictly follow the steps below for proper pump down procedure. Explosion may occur if the steps are not
followed as per sequence.
1 Press the “SERVICE” switch on remote control to enter SERVICE mode. Operate the system in Sr : 01 mode
for pump down operation.
2 After 10~15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10°C)), fully close 2 way
valve.
3 After 3 minutes, fully close 3 way valve.
4 Press the “OFF/ON” switch on remote control to stop pump down operation.
5 Remove the refrigerant piping.
14.3 How to Adjust Water Flow Rate
Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum.
The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is
medium speed (II). However, please ensure the minimum flow rate cannot be less than 18L/min.
Adjust it to high speed (III) or slow speed (I) if necessary (e.g. reduce the noise of running water).
Graph 5.1 shown the external static pressure (kPa) versus water flow rate (L/min).
Flow rate characteristic of indoor unit is as per above mentioned.
14.4 Expansion Vessel Pre Pressure Checking
Expansion Vessel with 10 L air capacity and initial pressure of 1 bar is installed in this Mono bloc unit.
Total amount of water in system should be below 200 L.
(Note: This amount of water is not include the tank unit volume)
If total amount of water is more than 200L, please install additional expansion vessel (field supply).
Please keep the installation height difference of system water circuit within 10 m.
(Inner volume of same Mono bloc unit is about 5 L)
Содержание WH-MDF09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Страница 15: ...15 4 1 1 Main Components ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 3 Weekly Timer Setting ...
Страница 20: ...20 4 1 4 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 49: ...49 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 66: ...66 ...
Страница 114: ...114 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge To Remove RCCB 17 5 To Remove RCCB ...
Страница 123: ...123 ...