13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 5 minutes.
Detection
conditions:
o
When detection of Tem above 30°C.
o
Calculation of average evaporation temperature (Tem).
o
Use outdoor low pressure sensor.
o
Tem use the value calculated for discharge temperature setting value.
After
detection:
o
Compressor stops restart again after 3 mins.
o
When abnormalities continuously generated 60 times within 480 minutes.
o
Protection
is
prohibited.
o
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 1 minute.
Detection
conditions:
o
When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
o
When abnormality is detected continue 5 seconds, unit stop operation.
o
OFF/ON remote control LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting
condition:
o
Heating
operation
o
Outdoor air temperature < -10°C
o
Actual
frequency
≥
50Hz
o
Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation
condition:
o
starting condition not fulfill.
o
Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C.
Содержание WH-MDF09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Страница 15: ...15 4 1 1 Main Components ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 3 Weekly Timer Setting ...
Страница 20: ...20 4 1 4 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 49: ...49 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 66: ...66 ...
Страница 114: ...114 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge To Remove RCCB 17 5 To Remove RCCB ...
Страница 123: ...123 ...