12. Operation and Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at mono bloc unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal water setting temperature and water
outlet temperature.
12.1.1 Internal Water Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the Air-to-Water Heatpump settings and the operation
environment. The final shifted value will be used as internal water setting temperature and it is updated continuously
whenever the electrical power is supplied to the unit.
12.1.2 Heating Operation
12.1.2.1 Thermostat
control
Compressor is OFF when Water Outlet Temperature - Internal Water Setting Temperature > 2°C for continuously
3 minutes.
Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature - Water Inlet Temperature
(temperature at thermostat OFF is triggered) < -3°C.
12.1.3 Tank Mode Operation
Control contents:
3 ways valve direction
- 3 ways valve switch and fix to tank side.
Heat pump Thermostat characteristic
- Water set temperature = Tank set temperature or
[50°C]
whichever lower.
- Heat pump Water Outlet set temperature is set to Maximum (53°C) at tank mode
i. Case 1
- THERMO OFF TEMP:
1 THERMO OFF TEMP = Water set tempe
[1°C]
.
2 Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump OFF, water pump OFF.
- THERMO ON TEMP:
1 THERMO ON TEMP = Water set tempe
[-1°C]
.
When detect tank temperature < THERMO ON TEMP, water pump ON for 3 minutes then heat pump ON.
ii. Case 2
- Heat pump THERMO OFF TEMP:
1 Heat pump THERMO OFF TEMP = 53°C +
[+4°C]
.
2 Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump OFF.
- Heat pump THERMO ON TEMP:
1 Heat pump THERMO ON TEMP = Water inlet during thermo off time +
[-3°C]
.
2 Heat pump ON back when water outlet temperature < Heat pump THERMO ON TEMP.
iii. Case 3
- Heat pump THERMO OFF TEMP:
1 Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
- Heat pump THERMO ON TEMP:
1 Heat pump THERMO ON TEMP = Water inlet temperature < 55°C.
Содержание WH-MDF09C3E8
Страница 14: ...14 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Страница 15: ...15 4 1 1 Main Components ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 3 Weekly Timer Setting ...
Страница 20: ...20 4 1 4 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Mono Bloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 25: ...25 7 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDF09C3E8 WH MDF09C3E8 1 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDF12C9E8 WH MDF14C9E8 WH MDF16C9E8 WH MDF12C9E8 1 WH MDF14C9E8 1 WH MDF16C9E8 1 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 1 1 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 49: ...49 ...
Страница 55: ...55 ...
Страница 56: ...56 ...
Страница 66: ...66 ...
Страница 114: ...114 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge To Remove RCCB 17 5 To Remove RCCB ...
Страница 123: ...123 ...