25.2.11 Water Flow Switch Abnormality (- / - / H62)
Malfunction Decision Conditions:
During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to
determine water flow error.
Malfunction Caused:
1. Faulty water pump.
2. Water leak in system.
3. Faulty connector connection.
4. Faulty water flow switch.
5. Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Check the system water pump
Is the CN4 connector
connection normal?
- Defect in flow sensor.
- Replace the flow sensor
Check the water system passage
Is the water pump working?
Is there any water leakage
Yes
Yes
Yes
Yes
No
No
No
No
Replace the faulty water
pump
- Connector poor contact.
- Correct the connection.
- Defect in indoor unit PCB
(main).
- Replace the indoor unit PCB
(main).
Fix the water leakage
Check the CN-FLWSEN connector connection:
- Turn OFF the power.
- Check the connector connection
Check the Vdc from the indoor unit PCB
(main):
- Disconnect flow sensor from the indoor
unit PCB terminal CN-FLWSEN
- Turn ON the power.
- Measure the Vdc as shown in Figure 1
(pin 1 and 3)
- Is the Vdc measurement 5Vdc?
Caution
BR
W
B
BL
FLOW
SENSOR
Figure 1
1
4
CN-FLWSEN
(WHT)
5Vdc
5V
R130
10k
C92
0.1u