25.2.37 Outdoor Discharge Pipe Temperature Sensor Abnormality (H30 / F04 / F40)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor
temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
Compressor Temp. Sensor
(Thermistor) Characteristics
70
60
50
R
e
si
st
a
n
ce
(
kΩ
)
40
30
20
10
0
Temperature (ºC)
20 40 60 80 100 120 140
When abnormality indication starts again
Check the outdoor compressor temperature sensor:
● Plug out connector from the outdoor unit PCB
● Measure the resistance of the outdoor compressor
temperature sensor
For safety reason and to prevent component
breakdown, always switch off the power
before remove and connect the component.
Is the measured resistance of the outdoor compressor
temperature sensor matches the value specified in its
characteristic chart?
Check the connector connection:
● Turn off the power
● Check the connector connection
Is the connector connection normal?
YES
NO
NO
YES
●
Connector poor contact
●
Correct the connection
●
Defect in outdoor compressor temperature sensor
●
Replace the outdoor compressor temperature sensor
●
Defect in outdoor unit PCB
●
Replace the outdoor unit PCB