Mini VRF SYSTEM
Trouble Diagnosis
3
3-42
3. Mini VRF System Alarm Codes
1-1
1-2
Check for
open circuit and
the voltage at the
breaker. if a problem
is found, fix it and
check again.
Yes
No
Turn the power back on and check again. Is the alarm triggered
again?
1-2
2-1
3-1
Yes
No
1 Check
the power
supply &
the wiring
Are the wires (RE1, RE2) from the reactor firmly installed?
2-1
2-2
Correct wiring
Yes
No
Turn the power back on and check again. Is the alarm triggered
again?
4hp, 5hp:
Common in RE1 and RE2
Plug-in type
6hp: Fastening screw type
*
2-2
Replace the outdoor
unit HIC PC board.
3-1
Yes
No
2 Check the
outdoor
unit CR
board
There may be a Instantaneous blackout failure.
If there is nothing abnormal, see what happens.
RE1
RE2*
3-1
3 Final check
P05 Power Supply Error
Error Detection Method
Error Diagnosis
Instantaneous blackout
•
Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before
performing the tests.
Zero-cross (waveform input of power supply) error
•
DC voltage charge failure
•
1.
2.
Is the voltage on each of the terminal boards 10% of the
rated voltage?
RE1
RE2
Sigle-phase outdoor unit HIC board
3-phase outdoor unit HIC board