Mini VRF SYSTEM
Trouble Diagnosis
3
3-31
3. Mini VRF System Alarm Codes
Check power supply
1-3
Extreme voltage fluctuations
Not satisfied with +10% rated supply voltage
1-1
1-2
Extreme distortion of voltage waveform
1-3
Instantaneous blackout may sometimes occur.
1-4
Check power supply
1-2
Check power supply
1-4
Check power supply
2-1
Yes
Yes
Yes
Yes
No
No
No
No
1 Power
supply*
H01 Primary Current (Input) Detect of Overcurrent
Error Detection Method
Error Diagnosis
Primary current effective value detected overcurrent (trip current value).
Trip current value
Single-phase model
hp = horse power
•
1.
2.
2
2-3
2-2
Loose electrical wire connection
2-1
Correct wiring
2-3
Has FUSE 1 blown?
Check the electrical conduction with tester.
2-2
Yes
Yes
No
No
Replace CR board.
2-3
PC board
wiring
Check not only in the outdoor unit stop mode but in the drive mode.
*
Heating
Cooling
4 hp
23.0A
22.0A
5 hp
26.5A
25.0A
6 hp
30.0A
28.0A
Trip current value
3-phase model
hp = horse power
Heating
Cooling
4 hp
10.5A
10.5A
5 hp
12.0A
12.0A
6 hp
14.0A
14.0A
(for single-phase outdoor unit PC board)
(for 3-phase outdoor unit PC board)
FUSE 1
FUSE 1