Mini VRF SYSTEM
Trouble Diagnosis
3
3-2
1. Contents of Remote Controller Switch Alarm Display
Remote controller is
detecting error signal from
indoor unit.
Indoor unit is detecting error
signal from outdoor unit.
Improper setting of indoor unit
or remote controller .
During auto address setting,
number of connected units
does not correspond to
number set.
When turning on the power
supply, number of connected
units does not correspond to
number set.
(Except R.C. address is “0.”)
Indoor unit communication
error of group control wiring
Improper setting
<E01>
<E02>
<E06>
<<E03>>
E04
E08
<<E09>>
E12
E15
E16
E24
E26
E29
E30
E25
E18
<L03>
L04
L05
L06
L07
L08
<<L09>>
Indoor unit is detecting error signal from remote controller (and system controller).
Error in receiving serial communication signal
(Signal from main indoor unit in case of group control)
Ex: Auto address is not completed.
Error in transmitting serial communication signal
Error in receiving serial communication signal
When turning on the power supply, the number of connected
indoor units does not correspond to the number set. (Except R.C.
address is “0.”)
Indoor unit address setting is duplicated.
Remote controller address connector (RCU. ADR) is duplicated.
(Duplication of main remote controller)
Starting auto address setting is prohibited.
This alarm message shows that the auto address connector
CN-A.ADD is shorted while other RC line is executing auto
address operation.
Error in auto address setting (Number of connected indoor units
is less than the number set.)
Error in auto address setting (Number of connected indoor units
is more than the number set.)
Error of outdoor unit address setting
The number of connected main and sub outdoor units do not
correspond to the number set at main outdoor unit PCB.
Error of sub outdoor unit in receiving serial communication
signal from main outdoor unit
Outdoor unit serial communications failure.
Error of main indoor unit in receiving serial communication signal
from sub indoor units
Duplication of main indoor unit address setting in group control
Duplication of outdoor R.C. address setting
Group control wiring is connected to individual control indoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
There are 2 or more indoor units
controllers which have operation
mode priority in 1 refrigerant circuit.
Priority set remote controller
Non-priority set remote controller
Error of the outdoor unit in receiving serial communication signal
from the indoor unit
No indoor unit is connected during auto address setting.
Main outdoor unit is detecting error signal from sub outdoor unit.
Serial
communication
errors
Missetting
Protective device in indoor
unit is activated.
<<P01>>
<<P09>>
<<P10>>
<<P12>>
Thermal protector in indoor unit fan motor is activated.
Improper wiring connections of ceiling panel
Float switch is activated.
Operation of protective function of fan inverter
Activation of
protective
device
Continued
This alarm message shows when the indoor unit for multiple-use is
not connected to the outdoor unit.
Capacity code of outdoor unit is not set.
L02
L10
L18
4-way valve operation failure
ON:
Operation
Standby
for heating
Blinking:
OFF:
Possible cause of malfunction
Wireless
remote controller
receiver display
Wired
remote
control
display
Timer
E20
Operating lamp
blinking
Operating lamp
blinking
Heating ready
lamp blinking
Heating ready
lamp blinking
Operating and
heating ready
lamps blinking
simultaneously
Operating and
heating ready
lamps blinking
simultaneously
Timer and heat
ready lamp
blinking
altemately
P14
Operation of O
2
sensor