![Panasonic U-4LE1R8 Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/panasonic/u-4le1r8/u-4le1r8_service-manual_4153774072.webp)
Mini VRF SYSTEM
Trouble Diagnosis
3
3-32
3. Mini VRF System Alarm Codes
H02 PAM Error
Error Detection Method
Error Diagnosis
Error is detected by over-voltage and overcurrent of DC side.
1.
2.
•
1-1
1-2
1-3
1-2
Check power supply
1-3
Yes
No
1 Power
supply*
Yes
No
2-1
2-2
2-3
Correct connection
2-2
Correct connection
or wiring
2-3
Yes
No
2 Control PC
board wiring
Yes
No
Extreme voltage fluctuations
Extreme distortion of voltage waveform
Check power supply
2-1
Yes
No
Check power supply
Loose electrical wire connection
Is HIC control PC board connector (CN-PAM) poorly connected or
opened with wire?
Replace HIC control PC board.
Check not only in the outdoor unit stop mode but in the drive mode.
*
Not satisfied with +10% rated supply voltage
SM830196-00.indb 32
2011/09/30 15:50:25
SM830209-00̲Mini̲VRF SYS.indb 32
SM830209-00̲Mini̲VRF SYS.indb 32
2012/01/11 18:25:21
2012/01/11 18:25:21